Assessment Year | 2005 |
---|---|
Principal Product | hotel and restaurant equipment |
NAICS | 337127: Institutional Furniture Manufacturing |
SIC | 2599: Furniture and Fixtures, Not Elsewhere Classified |
Sales Range | $10 M to 50M |
# of Employees | 180 |
Plant Area |
100,000
ft2
|
Annual Production | 1
units
|
Production Hrs. Annual | 2,625
hrs
|
Location (State) | California |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $113,532 | 1,341,625 |
kWh
|
$0.085 |
Electricity Demand | $87,054 | 6,256 |
kW-mo/yr
|
$13.92 |
Natural Gas | $59,215 | 7,343 |
MMBtu
|
$8.06 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $66,212 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $36,412 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Solid Waste (non-haz) Savings |
---|---|---|---|---|---|---|---|---|
01 | 4.631: Install an uninteruptable power supply | $27,800 | - | - | - | - |
$27,800
-
lb
|
|
02 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $10,927 | $7,500 |
$10,927
73,698
kWh
|
- | - | - | |
03 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $5,769 | $140 |
$3,293
38,930
kWh
|
$2,476
-
kW-mo/yr
|
- | - | |
04 | 2.6231: Utilize controls to operate equipment only when needed | $2,982 | $220 |
$2,982
35,249
kWh
|
- | - | - | |
05 | 2.2514: Cover open tanks | $2,000 | $4,500 | - | - |
$2,000
-
MMBtu
|
- | |
06 | 2.6212: Turn off equipment during breaks, reduce operating time | $688 | $350 |
$688
8,131
kWh
|
- | - | - | |
07 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $16,046 | $52,243 |
$9,156
108,221
kWh
|
$6,890
-
kW-mo/yr
|
- | - | |
TOTAL RECOMMENDED | $66,212 | $64,953 |
$27,046
264,229
kWh
|
$9,366
-
kW-mo/yr
|
$2,000
-
MMBtu
|
$27,800
-
lb
|
||
TOTAL IMPLEMENTED | $36,412 | $60,453 |
$27,046
264,229
kWh
|
$9,366
-
kW-mo/yr
|
- | - | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Solid Waste (non-haz) Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs