Assessment Year | 2003 |
---|---|
Principal Product | Printed Material |
NAICS | 511140: Directory and Mailing List Publishers |
SIC | 2747: |
Sales Range | $10 M to 50M |
# of Employees | 79 |
Plant Area |
49,000
ft2
|
Annual Production | 10,000,000
pieces
|
Production Hrs. Annual | 6,732
hrs
|
Location (State) | California |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $146,309 | 1,701,289 |
kWh
|
$0.086 |
Electricity Demand | $70,743 | 4,501 |
kW-mo/yr
|
$15.72 |
Natural Gas | $4,209 | 536 |
MMBtu
|
$7.85 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $54,026 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $11,418 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings |
---|---|---|---|---|---|---|
01 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $30,850 | $15,600 |
$22,456
249,787
kWh
|
$8,394
-
kW-mo/yr
|
|
02 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $11,418 | $380 |
$8,705
96,824
kWh
|
$2,713
-
kW-mo/yr
|
|
03 | 2.6231: Utilize controls to operate equipment only when needed | $5,587 | $320 |
$5,587
62,148
kWh
|
- | |
04 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $4,811 | $6,912 |
$3,664
40,753
kWh
|
$1,147
-
kW-mo/yr
|
|
05 | 2.7134: Use photocell controls | $1,360 | $1,000 |
$605
6,732
kWh
|
$755
-
kW-mo/yr
|
|
TOTAL RECOMMENDED | $54,026 | $24,212 |
$41,017
456,244
kWh
|
$13,009
-
kW-mo/yr
|
||
TOTAL IMPLEMENTED | $11,418 | $380 |
$8,705
96,824
kWh
|
$2,713
-
kW-mo/yr
|
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs