| Assessment Year | 1990 |
|---|---|
| Principal Product | THERMOPLASTIC PARTS |
| NAICS |
n/a
|
| SIC | 3089: Plastics Products, Not Elsewhere Classified |
| Sales Range | $1 M to 5M |
| # of Employees | 115 |
| Plant Area |
n/a
|
| Annual Production | 100,000
pieces
|
| Production Hrs. Annual | 3,920
hrs
|
| Location (State) | New Jersey |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $140,940 | 1,423,212 |
kWh
|
$0.099 |
| Fuel Oil #4 | $40,755 | 11,236 |
MMBtu
|
$3.63 |
| TOTAL YEARLY COSTS | - | |||
| RECOMMENDED SAVINGS* | $15,808 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | $10,599 | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Fuel Oil #4 Savings |
|---|---|---|---|---|---|---|
| 01 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $3,666 | $650 |
$3,666
36,928
kWh
|
- | |
| 02 | 2.1233: Analyze flue gas for proper air/fuel ratio | $3,179 | $500 | - |
$3,179
-
MMBtu
|
|
| 03 | 2.4312: Improve lubrication practices | $699 | $800 |
$699
7,034
kWh
|
- | |
| 04 | 2.2136: Install / repair insulation on steam lines | $229 | $81 | - |
$229
-
MMBtu
|
|
| 05 | 2.7312: Minimize use of outside make-up air for ventilation except when used for economizer cycle | $1,331 | $412 | - |
$1,331
-
MMBtu
|
|
| 06 | 2.2122: Install / repair insulation on condensate lines | $420 | $279 | - |
$420
-
MMBtu
|
|
| 07 | 2.2135: Repair and eliminate steam leaks | $6,284 | $325 | - |
$6,284
-
MMBtu
|
|
| TOTAL RECOMMENDED | $15,808 | $3,047 |
$4,365
43,962
kWh
|
$11,443
-
MMBtu
|
||
| TOTAL IMPLEMENTED | $10,599 | $1,335 |
$3,666
36,928
kWh
|
$6,933
-
MMBtu
|
||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Fuel Oil #4 Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs