| Assessment Year | 2014 |
|---|---|
| Principal Product | Dimensional Lumber |
| NAICS | 321113: Sawmills |
| SIC | 2421: Sawmills and Planing Mills, General |
| Sales Range | $100 M to 500M |
| # of Employees | 450 |
| Plant Area |
450,000
ft2
|
| Annual Production | 120,000,000
units
|
| Production Hrs. Annual | 3,120
hrs
|
| Location (State) | Oregon |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $1,375,810 | 26,073,312 |
kWh
|
$0.053 |
| Electricity Demand | $506,626 | 69,593 |
kW-mo/yr
|
$7.28 |
| LPG | $46,361 | 2,568 |
MMBtu
|
$18.05 |
| TOTAL YEARLY COSTS | - | |||
| RECOMMENDED SAVINGS* | $240,857 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | - | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Administrative Changes Savings | Ancillary Material Cost Savings |
|---|---|---|---|---|---|---|---|---|
| 01 | 2.4224: Upgrade controls on compressors | $102,712 | $87,114 |
$94,527
1,793,677
kWh
|
$8,185
-
kW-mo/yr
|
- | - | |
| 02 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $6,951 | - |
$3,913
74,248
kWh
|
$3,038
-
kW-mo/yr
|
- | - | |
| 03 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $101,299 | $258,445 |
$70,693
1,341,432
kWh
|
$12,516
-
kW-mo/yr
|
$2,870 | $15,220 | |
| 04 | 2.6218: Turn off equipment when not in use | $4,747 | $1,502 |
$4,747
90,067
kWh
|
- | - | - | |
| 05 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $2,923 | $1,344 |
$2,923
55,458
kWh
|
- | - | - | |
| 06 | 2.4112: Install soft-start to eliminate nuisance trips | $22,225 | - |
$23,225
440,710
kWh
|
- | $(-1,000.0) | - | |
| TOTAL RECOMMENDED | $240,857 | $348,405 |
$200,028
3,795,592
kWh
|
$23,739
-
kW-mo/yr
|
$1,870 | $15,220 | ||
| TOTAL IMPLEMENTED | - | - | - | - | - | - | ||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Administrative Changes Savings | Ancillary Material Cost Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs