Assessment Year | 2013 |
---|---|
Principal Product | Freeze Dried Food |
NAICS | 311411: Frozen Fruit, Juice, and Vegetable Manufacturing |
SIC | 2037: Frozen Fruits, Fruit Juices, and Vegetables |
Sales Range | $10 M to 50M |
# of Employees | 70 |
Plant Area |
84,620
ft2
|
Annual Production | 3,858
units
|
Production Hrs. Annual | 8,760
hrs
|
Location (State) | Oregon |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $778,749 | 15,424,774 |
kWh
|
$0.050 |
Electricity Demand | $242,732 | 30,039 |
kW-mo/yr
|
$8.08 |
Electricity Fees | $74,315 | - |
|
- |
Natural Gas | $192,648 | 39,253 |
MMBtu
|
$4.91 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $266,611 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $64,511 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Personnel Changes Savings |
---|---|---|---|---|---|---|---|---|
01 | 2.1116: Improve combustion control capability | $11,054 | $11,584 |
$4,630
87,943
kWh
|
- |
$6,424
-
MMBtu
|
- | |
02 | 2.2492: Use "heat wheel" or other heat exchanger to cross-exchange building exhaust air with make-up air | $8,287 | $11,998 |
$8,287
157,390
kWh
|
- | - | - | |
03 | 4.132: Purchase new equipment to reduce material use / cost | $161,127 | $238,200 |
$17,979
341,482
kWh
|
$3,948
-
kW-mo/yr
|
- | $139,200 | |
04 | 2.6218: Turn off equipment when not in use | $1,406 | $2,100 |
$1,406
25,002
kWh
|
- | - | - | |
05 | 2.2611: Moderate cooling tower outlet temperature | $64,511 | $85,275 |
$53,015
1,006,988
kWh
|
$11,496
-
kW-mo/yr
|
- | - | |
06 | 2.4224: Upgrade controls on compressors | $8,077 | $26,477 |
$7,307
138,792
kWh
|
$770
-
kW-mo/yr
|
- | - | |
07 | 2.2628: Utilize a less expensive cooling method | $6,621 | $24,248 |
$5,513
98,007
kWh
|
$1,108
-
kW-mo/yr
|
- | - | |
08 | 2.2127: Flash condensate to produce lower pressure steam | $4,383 | $16,215 | - | - |
$4,383
-
MMBtu
|
- | |
09 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $1,145 | $5,840 |
$1,145
21,748
kWh
|
- | - | - | |
TOTAL RECOMMENDED | $266,611 | $421,937 |
$99,282
1,877,352
kWh
|
$17,322
-
kW-mo/yr
|
$10,807
-
MMBtu
|
$139,200 | ||
TOTAL IMPLEMENTED | $64,511 | $85,275 |
$53,015
1,006,988
kWh
|
$11,496
-
kW-mo/yr
|
- | - | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Personnel Changes Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs