Assessment Year | 2013 |
---|---|
Principal Product | Carbon Materials |
NAICS | 335991: Carbon and Graphite Product Manufacturing |
SIC | 3624: Carbon and Graphite Products |
Sales Range | $10 M to 50M |
# of Employees | 35 |
Plant Area |
76,000
ft2
|
Annual Production | 600,000
units
|
Production Hrs. Annual | 8,760
hrs
|
Location (State) | Oregon |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $111,791 | 2,049,320 |
kWh
|
$0.055 |
Electricity Demand | $72,356 | 9,196 |
kW-mo/yr
|
$7.87 |
Electricity Fees | $12,011 | - |
|
- |
Natural Gas | $71,310 | 11,932 |
MMBtu
|
$5.98 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $231,831 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $19,862 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings |
---|---|---|---|---|---|---|---|
01 | 2.4231: Reduce the pressure of compressed air to the minimum required | $8,634 | $500 |
$7,804
144,189
kWh
|
$830
-
kW-mo/yr
|
- | |
02 | 2.1116: Improve combustion control capability | $144,955 | $110,000 | - | - |
$144,955
-
MMBtu
|
|
03 | 2.2437: Recover waste heat from equipment | $53,512 | $43,218 | - | - |
$53,512
-
MMBtu
|
|
04 | 2.2443: Re-use or recycle hot or cold process exhaust air | $13,502 | $5,712 |
$11,209
207,194
kWh
|
$2,293
-
kW-mo/yr
|
- | |
05 | 2.4224: Upgrade controls on compressors | $11,228 | $11,850 |
$9,715
179,509
kWh
|
$1,513
-
kW-mo/yr
|
- | |
TOTAL RECOMMENDED | $231,831 | $171,280 |
$28,728
530,892
kWh
|
$4,636
-
kW-mo/yr
|
$198,467
-
MMBtu
|
||
TOTAL IMPLEMENTED | $19,862 | $12,350 |
$17,519
323,698
kWh
|
$2,343
-
kW-mo/yr
|
- |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs