Assessment Year | 2007 |
---|---|
Principal Product | plywood |
NAICS | 321212: Softwood Veneer and Plywood Manufacturing |
SIC | 2493: Reconstituted Wood Products |
Sales Range | $50 M to 100M |
# of Employees | 305 |
Plant Area |
700,000
ft2
|
Annual Production | 250,000
thousand feet
|
Production Hrs. Annual | 7,300
hrs
|
Location (State) | Oregon |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $918,488 | 25,923,000 |
kWh
|
$0.035 |
Electricity Demand | $212,010 | 55,500 |
kW-mo/yr
|
$3.82 |
Electricity Fees | $39,915 | - |
|
- |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $220,870 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $220,870 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Wood Savings |
---|---|---|---|---|---|---|---|
01 | 2.2127: Flash condensate to produce lower pressure steam | $92,300 | $44,300 | - | - |
$92,300
-
MMBtu
|
|
02 | 2.4131: Size electric motors for peak operating efficiency | $37,000 | $20,600 |
$37,000
157,200
kWh
|
- | - | |
03 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $27,300 | - |
$27,300
658,400
kWh
|
- | - | |
04 | 2.6218: Turn off equipment when not in use | $27,800 | $12,500 |
$27,800
78,840
kWh
|
- | - | |
05 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $9,600 | $9,600 |
$9,600
225,200
kWh
|
- | - | |
06 | 2.4231: Reduce the pressure of compressed air to the minimum required | $7,300 | - |
$7,300
170,500
kWh
|
- | - | |
07 | 2.4224: Upgrade controls on compressors | $7,100 | $45,000 |
$6,185
176,700
kWh
|
$915
-
kW-mo/yr
|
- | |
08 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $5,250 | $9,300 |
$4,800
136,900
kWh
|
$450
-
kW-mo/yr
|
- | |
09 | 2.7135: Install occupancy sensors | $3,720 | $5,100 |
$3,600
102,044
kWh
|
$120
-
kW-mo/yr
|
- | |
10 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $1,600 | $4,500 |
$1,600
45,900
kWh
|
- | - | |
11 | 2.4322: Use or replace with energy efficient substitutes | $1,900 | $1,800 |
$1,900
38,000
kWh
|
- | - | |
TOTAL RECOMMENDED | $220,870 | $152,700 |
$127,085
1,789,684
kWh
|
$1,485
-
kW-mo/yr
|
$92,300
-
MMBtu
|
||
TOTAL IMPLEMENTED | $220,870 | $152,700 |
$127,085
1,789,684
kWh
|
$1,485
-
kW-mo/yr
|
$92,300
-
MMBtu
|
||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Wood Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs