Assessment Year | 2005 |
---|---|
Principal Product | Wool Textiles |
NAICS | 313210: Broadwoven Fabric Mills |
SIC | 2231: Broadwoven Fabric Mills, Wool (Including Dyeing and Finishing) |
Sales Range | $10 M to 50M |
# of Employees | 270 |
Plant Area |
300,000
ft2
|
Annual Production | 4,500,000
thousand feet
|
Production Hrs. Annual | 8,760
hrs
|
Location (State) | Washington |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $385,000 | 9,200,000 |
kWh
|
$0.042 |
Electricity Demand | $131,000 | 288,000 |
kW-mo/yr
|
$0.45 |
Natural Gas | $700,000 | 116,000 |
MMBtu
|
$6.03 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $334,467 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $10,367 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Water Disposal Savings | Water Consumption Savings |
---|---|---|---|---|---|---|---|---|---|
01 | 3.4151: Minimize water usage | $215,000 | $620,000 | - | - |
$148,000
-
MMBtu
|
$24,000
-
Tgal
|
$43,000
-
Tgal
|
|
02 | 3.4151: Minimize water usage | $51,000 | $107,000 | - | - |
$51,000
-
MMBtu
|
- | - | |
03 | 2.2128: Use steam condensate for hot water supply (non-potable) | $39,000 | $16,400 | - | - |
$39,000
-
MMBtu
|
- | - | |
04 | 2.2136: Install / repair insulation on steam lines | $17,600 | $23,000 | - | - |
$17,600
-
MMBtu
|
- | - | |
05 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $4,630 | - |
$3,500
57,730
kWh
|
$1,130
-
kW-mo/yr
|
- | - | - | |
06 | 2.4239: Eliminate or reduce compressed air usage | $3,637 | $3,150 |
$3,637
82,492
kWh
|
- | - | - | - | |
07 | 2.7135: Install occupancy sensors | $2,100 | $104 |
$2,100
49,600
kWh
|
- | - | - | - | |
08 | 2.4224: Upgrade controls on compressors | $1,500 | $600 |
$1,400
34,000
kWh
|
$100
-
kW-mo/yr
|
- | - | - | |
TOTAL RECOMMENDED | $334,467 | $770,254 |
$10,637
223,822
kWh
|
$1,230
-
kW-mo/yr
|
$255,600
-
MMBtu
|
$24,000
-
Tgal
|
$43,000
-
Tgal
|
||
TOTAL IMPLEMENTED | $10,367 | $3,254 |
$9,237
189,822
kWh
|
$1,130
-
kW-mo/yr
|
- | - | - | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Water Disposal Savings | Water Consumption Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs