| Assessment Year | 2003 |
|---|---|
| Principal Product | Dimensional Lumber |
| NAICS |
n/a
|
| SIC | 2421: Sawmills and Planing Mills, General |
| Sales Range | n/a |
| # of Employees | 0 |
| Plant Area |
n/a
|
| Annual Production | 0
thousand feet
|
| Production Hrs. Annual | 2,448
hrs
|
| Location (State) | Washington |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $183,229 | 3,326,600 |
kWh
|
$0.055 |
| Electricity Demand | $38,029 | 13,447 |
kW-mo/yr
|
$2.83 |
| Electricity Fees | $3,149 | - |
|
- |
| LPG | $88,200 | 8,070 |
MMBtu
|
$10.93 |
| TOTAL YEARLY COSTS | - | |||
| RECOMMENDED SAVINGS* | $48,570 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | $31,860 | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Personnel Changes Savings | Administrative Changes Savings |
|---|---|---|---|---|---|---|---|---|---|
| 01 | 2.4322: Use or replace with energy efficient substitutes | $7,000 | $580 |
$5,600
102,000
kWh
|
$1,400
-
kW-mo/yr
|
- | - | - | |
| 02 | 2.4224: Upgrade controls on compressors | $3,700 | $2,000 |
$3,700
66,000
kWh
|
- | - | - | - | |
| 03 | 2.7124: Make a practice of turning off lights when not needed | $11,950 | $880 |
$9,200
166,000
kWh
|
- | - | - | $2,750 | |
| 04 | 2.1233: Analyze flue gas for proper air/fuel ratio | $3,000 | $150 | - | - |
$3,300
-
MMBtu
|
$(-300.0) | - | |
| 05 | 2.2136: Install / repair insulation on steam lines | $9,910 | $14,200 |
$9,910
180,000
kWh
|
- | - | - | - | |
| 06 | 2.4133: Use most efficient type of electric motors | $12,200 | $24,350 |
$9,150
164,450
kWh
|
$3,050
-
kW-mo/yr
|
- | - | - | |
| 07 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $810 | - |
$630
11,300
kWh
|
$180
-
kW-mo/yr
|
- | - | - | |
| TOTAL RECOMMENDED | $48,570 | $42,160 |
$38,190
689,750
kWh
|
$4,630
-
kW-mo/yr
|
$3,300
-
MMBtu
|
$(-300.0) | $2,750 | ||
| TOTAL IMPLEMENTED | $31,860 | $15,810 |
$24,710
448,000
kWh
|
$1,400
-
kW-mo/yr
|
$3,300
-
MMBtu
|
$(-300.0) | $2,750 | ||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Personnel Changes Savings | Administrative Changes Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs