Assessment Year | 2001 |
---|---|
Principal Product | Medium Density Fiberboard |
NAICS |
n/a
|
SIC | 2493: Reconstituted Wood Products |
Sales Range | $10 M to 50M |
# of Employees | 71 |
Plant Area |
n/a
|
Annual Production | 65,665,014
thousand feet
|
Production Hrs. Annual | 7,884
hrs
|
Location (State) | Oregon |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $1,429,092 | 59,315,630 |
kWh
|
$0.024 |
Electricity Demand | $420,441 | 1,317,768 |
kW-mo/yr
|
$0.32 |
Natural Gas | $2,308,961 | 523,542 |
MMBtu
|
$4.41 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $62,925 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $51,345 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Ancillary Material Cost Savings |
---|---|---|---|---|---|---|---|
01 | 2.4322: Use or replace with energy efficient substitutes | $31,896 | $31,163 |
$26,410
868,201
kWh
|
$5,486
-
kW-mo/yr
|
- | |
02 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $6,492 | $5,000 |
$5,331
221,216
kWh
|
$1,161
-
kW-mo/yr
|
- | |
03 | 2.4224: Upgrade controls on compressors | $11,580 | $4,080 |
$9,630
399,164
kWh
|
$1,950
-
kW-mo/yr
|
- | |
04 | 2.7134: Use photocell controls | $1,883 | $2,150 |
$1,299
53,874
kWh
|
- | $584 | |
05 | 2.4133: Use most efficient type of electric motors | $11,074 | $29,915 |
$8,886
368,723
kWh
|
$2,188
-
kW-mo/yr
|
- | |
TOTAL RECOMMENDED | $62,925 | $72,308 |
$51,556
1,911,178
kWh
|
$10,785
-
kW-mo/yr
|
$584 | ||
TOTAL IMPLEMENTED | $51,345 | $68,228 |
$41,926
1,512,014
kWh
|
$8,835
-
kW-mo/yr
|
$584 |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs