| Assessment Year | 2001 |
|---|---|
| Principal Product | Medium Density Fiberboard |
| NAICS |
n/a
|
| SIC | 2493: Reconstituted Wood Products |
| Sales Range | $10 M to 50M |
| # of Employees | 71 |
| Plant Area |
n/a
|
| Annual Production | 65,665,014
thousand feet
|
| Production Hrs. Annual | 7,884
hrs
|
| Location (State) | Oregon |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $1,429,092 | 59,315,630 |
kWh
|
$0.024 |
| Electricity Demand | $420,441 | 1,317,768 |
kW-mo/yr
|
$0.32 |
| Natural Gas | $2,308,961 | 523,542 |
MMBtu
|
$4.41 |
| TOTAL YEARLY COSTS | - | |||
| RECOMMENDED SAVINGS* | $62,925 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | $51,345 | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Ancillary Material Cost Savings |
|---|---|---|---|---|---|---|---|
| 01 | 2.4322: Use or replace with energy efficient substitutes | $31,896 | $31,163 |
$26,410
868,201
kWh
|
$5,486
-
kW-mo/yr
|
- | |
| 02 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $6,492 | $5,000 |
$5,331
221,216
kWh
|
$1,161
-
kW-mo/yr
|
- | |
| 03 | 2.4224: Upgrade controls on compressors | $11,580 | $4,080 |
$9,630
399,164
kWh
|
$1,950
-
kW-mo/yr
|
- | |
| 04 | 2.7134: Use photocell controls | $1,883 | $2,150 |
$1,299
53,874
kWh
|
- | $584 | |
| 05 | 2.4133: Use most efficient type of electric motors | $11,074 | $29,915 |
$8,886
368,723
kWh
|
$2,188
-
kW-mo/yr
|
- | |
| TOTAL RECOMMENDED | $62,925 | $72,308 |
$51,556
1,911,178
kWh
|
$10,785
-
kW-mo/yr
|
$584 | ||
| TOTAL IMPLEMENTED | $51,345 | $68,228 |
$41,926
1,512,014
kWh
|
$8,835
-
kW-mo/yr
|
$584 | ||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs