Assessment Year | 2000 |
---|---|
Principal Product | Manufatured Homes |
NAICS |
n/a
|
SIC | 2451: Mobile Homes |
Sales Range | $10 M to 50M |
# of Employees | 180 |
Plant Area |
240,000
ft2
|
Annual Production | 2,080
pieces
|
Production Hrs. Annual | 2,340
hrs
|
Location (State) | Oregon |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $72,587 | 1,669,695 |
kWh
|
$0.043 |
Electricity Demand | $17,554 | 80,076 |
kW-mo/yr
|
$0.22 |
Electricity Fees | $547 | - |
|
- |
Natural Gas | $67,378 | 10,901 |
MMBtu
|
$6.18 |
Wood | $13,166 | - |
|
- |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $32,445 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $30,516 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Natural Gas Savings |
---|---|---|---|---|---|---|---|---|
01 | 2.4231: Reduce the pressure of compressed air to the minimum required | $1,963 | - |
$1,157
32,825
kWh
|
$806
-
kW-mo/yr
|
- | - | |
02 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $365 | - |
$215
6,155
kWh
|
$150
-
kW-mo/yr
|
- | - | |
03 | 2.3212: Optimize plant power factor | $359 | $1,200 | - | - | $359 | - | |
04 | 2.7243: Improve air circulation with destratification fans / other methods | $1,570 | $7,800 |
$1,043
19,343
kWh
|
$527
-
kW-mo/yr
|
- | - | |
05 | 2.7261: Install timers and/or thermostats | $28,188 | $1,410 | - | - | - |
$28,188
-
MMBtu
|
|
TOTAL RECOMMENDED | $32,445 | $10,410 |
$2,415
58,323
kWh
|
$1,483
-
kW-mo/yr
|
$359 |
$28,188
-
MMBtu
|
||
TOTAL IMPLEMENTED | $30,516 | $1,410 |
$1,372
38,980
kWh
|
$956
-
kW-mo/yr
|
- |
$28,188
-
MMBtu
|
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs