Assessment Year | 1999 |
---|---|
Principal Product | Sound absorbing Materials |
NAICS |
n/a
|
SIC | 3296: Mineral Wool |
Sales Range | $10 M to 50M |
# of Employees | 213 |
Plant Area |
345,600
ft2
|
Annual Production | 648,500
pieces
|
Production Hrs. Annual | 6,240
hrs
|
Location (State) | Oregon |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $680,886 | 23,245,311 |
kWh
|
$0.029 |
Electricity Demand | $105,744 | 528,720 |
kW-mo/yr
|
$0.20 |
Electricity Fees | $7,681 | - |
|
- |
Natural Gas | $2,053,252 | 840,030 |
MMBtu
|
$2.44 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $1,057,620 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $845,200 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Water Disposal Savings | Solid Waste (non-haz) Savings | Personnel Changes Savings | Administrative Changes Savings | Primary Raw Material Savings | Water Consumption Savings | Primary Product Savings |
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
01 | 3.2124: Convert to air assisted / airless paint guns | $661,700 | $72,000 | - | - | - | - | - | - | - | $661,700 | - | - | |
02 | 3.4113: Treat and reuse rinse waters | $162,000 | $183,000 | - | - | - |
$105,000
-
Tgal
|
$1,600
-
lb
|
- | $13,900 | - |
$41,500
-
Tgal
|
- | |
03 | 3.5217: Reuse / recycle/ sell paper products | $5,880 | - | - | - | - | - |
$5,880
-
lb
|
- | - | - | - | - | |
04 | 3.5311: Recover and reuse waste material | $1,300 | $6,600 | - | - | - | - |
$740
-
lb
|
- | - | $560 | - | - | |
05 | 4.446: Automate finishing process | $106,000 | $106,500 | - | - | - | - | - | $103,000 | $3,000 | - | - | - | |
06 | 4.642: Install sensors to detect and avoid jams | $4,930 | $4,250 | - | - | - | - | - | - | - | - | - | $4,930 | |
07 | 2.2437: Recover waste heat from equipment | $93,630 | $40,200 |
$(-18,800.0)
(-643,025)
kWh
|
$(-2,970.0)
-
kW-mo/yr
|
$115,400
-
MMBtu
|
- | - | - | - | - | - | - | |
08 | 2.6218: Turn off equipment when not in use | $5,610 | $500 | - | - |
$5,610
-
MMBtu
|
- | - | - | - | - | - | - | |
09 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $16,570 | $8,000 |
$14,310
488,570
kWh
|
$2,260
-
kW-mo/yr
|
- | - | - | - | - | - | - | - | |
TOTAL RECOMMENDED | $1,057,620 | $421,050 |
$(-4,490.0)
(-154,455)
kWh
|
$(-710.0)
-
kW-mo/yr
|
$121,010
-
MMBtu
|
$105,000
-
Tgal
|
$8,220
-
lb
|
$103,000 | $16,900 | $662,260 |
$41,500
-
Tgal
|
$4,930 | ||
TOTAL IMPLEMENTED | $845,200 | $267,250 |
$14,310
488,570
kWh
|
$2,260
-
kW-mo/yr
|
- |
$105,000
-
Tgal
|
$1,600
-
lb
|
- | $13,900 | $661,700 |
$41,500
-
Tgal
|
$4,930 | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Water Disposal Savings | Solid Waste (non-haz) Savings | Personnel Changes Savings | Administrative Changes Savings | Primary Raw Material Savings | Water Consumption Savings | Primary Product Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs