Assessment Year | 1998 |
---|---|
Principal Product | Wood Mouldings |
NAICS |
n/a
|
SIC | 2431: Millwork |
Sales Range | $50 M to 100M |
# of Employees | 500 |
Plant Area |
450,000
ft2
|
Annual Production | 24,537,182
thousand feet
|
Production Hrs. Annual | 4,455
hrs
|
Location (State) | Oregon |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $670,439 | 18,233,588 |
kWh
|
$0.037 |
Electricity Demand | $203,421 | 747,072 |
kW-mo/yr
|
$0.27 |
Electricity Fees | $28,931 | - |
|
- |
Natural Gas | $192,846 | 43,618 |
MMBtu
|
$4.42 |
LPG | $23,051 | 3,700 |
MMBtu
|
$6.23 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $1,188,771 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $1,122,748 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Other Liquid (haz) Savings | Personnel Changes Savings | Administrative Changes Savings | Primary Raw Material Savings | Ancillary Material Cost Savings |
---|---|---|---|---|---|---|---|---|---|---|---|---|
01 | 4.512: Condense operation into one building | $1,080,150 | $1,000,000 | - | - | - | - | $50,150 | $1,030,000 | - | - | |
02 | 4.445: Install equipment to move product | $14,550 | $31,520 |
$(-30.0)
(-879)
kWh
|
$(-20.0)
-
kW-mo/yr
|
- | - | $14,600 | - | - | - | |
03 | 2.4322: Use or replace with energy efficient substitutes | $48,900 | $220,000 |
$35,200
1,057,444
kWh
|
$13,700
-
kW-mo/yr
|
- | - | - | - | - | - | |
04 | 2.3212: Optimize plant power factor | $15,977 | $44,400 | - | - | $15,977 | - | - | - | - | - | |
05 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $6,499 | $6,000 |
$4,687
140,680
kWh
|
$1,812
-
kW-mo/yr
|
- | - | - | - | - | - | |
06 | 2.4224: Upgrade controls on compressors | $14,409 | $9,600 |
$10,618
318,875
kWh
|
$3,791
-
kW-mo/yr
|
- | - | - | - | - | - | |
07 | 2.7111: Reduce illumination to minimum necessary levels | $1,890 | - |
$1,279
38,394
kWh
|
- | - | - | $193 | - | - | $418 | |
08 | 3.1191: Change procedures / equipment / operating conditions | $5,250 | - | - | - | - |
$250
-
gal
|
- | - | $5,000 | - | |
09 | 3.8141: Regenerate cleaning solvent on-site and reuse | $1,146 | $350 | - | - | - |
$1,146
-
gal
|
- | - | - | - | |
TOTAL RECOMMENDED | $1,188,771 | $1,311,870 |
$51,754
1,554,514
kWh
|
$19,283
-
kW-mo/yr
|
$15,977 |
$1,396
-
gal
|
$64,943 | $1,030,000 | $5,000 | $418 | ||
TOTAL IMPLEMENTED | $1,122,748 | $1,047,120 |
$16,554
497,070
kWh
|
$5,583
-
kW-mo/yr
|
- |
$250
-
gal
|
$64,943 | $1,030,000 | $5,000 | $418 | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Other Liquid (haz) Savings | Personnel Changes Savings | Administrative Changes Savings | Primary Raw Material Savings | Ancillary Material Cost Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs