Assessment Year | 1992 |
---|---|
Principal Product | ELECTRIC HEATERS |
NAICS |
n/a
|
SIC | 3634: Electric Housewares and Fans |
Sales Range | $10 M to 50M |
# of Employees | 120 |
Plant Area |
n/a
|
Annual Production | 382,600
pieces
|
Production Hrs. Annual | 6,000
hrs
|
Location (State) | Washington |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $36,234 | 1,211,313 |
kWh
|
$0.030 |
Natural Gas | $71,244 | 17,513 |
MMBtu
|
$4.07 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $13,517 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $13,517 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Natural Gas Savings | Administrative Changes Savings |
---|---|---|---|---|---|---|---|
01 | 2.6232: Install set-back timers | $1,784 | - |
$1,225
56,272
kWh
|
- | $559 | |
02 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $214 | - |
$214
7,327
kWh
|
- | - | |
03 | 2.2426: Use waste heat from flue gases to heat space conditioning air | $7,907 | $2,071 | - |
$7,907
-
MMBtu
|
- | |
04 | 2.4239: Eliminate or reduce compressed air usage | $288 | $200 |
$288
10,551
kWh
|
- | - | |
05 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $1,213 | $1,000 |
$1,213
44,842
kWh
|
- | - | |
06 | 2.4133: Use most efficient type of electric motors | $182 | $858 |
$182
6,741
kWh
|
- | - | |
07 | 2.2511: Insulate bare equipment | $1,929 | $3,837 | - |
$1,929
-
MMBtu
|
- | |
TOTAL RECOMMENDED | $13,517 | $7,966 |
$3,122
125,733
kWh
|
$9,836
-
MMBtu
|
$559 | ||
TOTAL IMPLEMENTED | $13,517 | $7,966 |
$3,122
125,733
kWh
|
$9,836
-
MMBtu
|
$559 | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Natural Gas Savings | Administrative Changes Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs