Assessment Year 1992
Principal Product FROZEN FRUIT, CORN
NAICS
n/a
SIC 2037: Frozen Fruits, Fruit Juices, and Vegetables
Sales Range $50
M
to 100
M
# of Employees 175
Plant Area
n/a
Annual Production 44,000,000
lb
Production Hrs. Annual 8,736
hrs
Location (State) Oregon

Facility Energy Cost and Usage

Source Yearly Cost Usage
Electricity Usage $246,293 8,346,131
kWh
Natural Gas $98,737 46,079
MMBtu
TOTAL YEARLY COSTS -
RECOMMENDED SAVINGS* $22,348 *Non-energy impacts included in savings.
IMPLEMENTED SAVINGS* $8,945

Recommendations

# Description Yearly Savings* Imp'd Cost* Status Electricity Usage Savings Natural Gas Savings Administrative Changes Savings
01 2.2694: Use highest temperature for chilling or cold storage $685 - $685
31,360
kWh
- -
02 2.2621: Modify refrigeration system to operate at a lower pressure $5,603 $18,000 $5,603
308,030
kWh
- -
03 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves $899 $1,000 $899
38,394
kWh
- -
04 2.4231: Reduce the pressure of compressed air to the minimum required $479 $740 $479
20,516
kWh
- -
05 2.4239: Eliminate or reduce compressed air usage $1,413 $40 $1,413
77,667
kWh
- -
06 2.6232: Install set-back timers $3,101 $774 $1,461
76,788
kWh
- $1,640
07 2.7142: Utilize higher efficiency lamps and/or ballasts $154 $3,789 $552
26,084
kWh
- $(-398.0)
08 2.4111: Utilize energy-efficient belts and other improved mechanisms $176 - $176
6,448
kWh
- -
09 2.4133: Use most efficient type of electric motors $102 $2,894 $102
4,103
kWh
- -
10 2.3212: Optimize plant power factor $6,939 $16,250 $6,939
-
kWh
- -
11 2.1233: Analyze flue gas for proper air/fuel ratio $2,293 $500 - $2,293
-
MMBtu
-
12 2.2123: Insulate feedwater tank $504 $272 - $504
-
MMBtu
-
TOTAL RECOMMENDED $22,348 $44,259 $18,309
589,390
kWh
$2,797
-
MMBtu
$1,242
TOTAL IMPLEMENTED $8,945 $10,009 $4,906
243,552
kWh
$2,797
-
MMBtu
$1,242
Yearly Savings* Imp'd Cost* Electricity Usage Savings Natural Gas Savings Administrative Changes Savings
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs