| Assessment Year | 1988 |
|---|---|
| Principal Product | HARDWOOD PLYWOOD |
| NAICS |
n/a
|
| SIC | 2435: Hardwood Veneer and Plywood |
| Sales Range | $10 M to 50M |
| # of Employees | 350 |
| Plant Area |
n/a
|
| Annual Production | 140
thousand feet
|
| Production Hrs. Annual | 7,800
hrs
|
| Location (State) | Oregon |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $901,685 | 21,635,991 |
kWh
|
$0.042 |
| Natural Gas | $12,487 | 2,709 |
MMBtu
|
$4.61 |
| Wood | $149,020 | 269,541 |
MMBtu
|
$0.55 |
| TOTAL YEARLY COSTS | - | |||
| RECOMMENDED SAVINGS* | $67,428 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | $28,320 | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Administrative Changes Savings |
|---|---|---|---|---|---|---|
| 01 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $2,776 | - |
$569
13,482
kWh
|
$2,207 | |
| 02 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $22,164 | $5,000 |
$22,164
531,946
kWh
|
- | |
| 03 | 2.4221: Install compressor air intakes in coolest locations | $2,349 | $500 |
$2,349
56,272
kWh
|
- | |
| 04 | 2.4133: Use most efficient type of electric motors | $1,087 | $623 |
$1,087
26,084
kWh
|
- | |
| 05 | 2.3212: Optimize plant power factor | $2,293 | $4,800 |
$2,293
-
kWh
|
- | |
| 06 | 2.6222: Use drying oven (batch type) on alternate days or other optimum schedule to run equipment with full loads | $36,759 | - |
$36,759
875,147
kWh
|
- | |
| TOTAL RECOMMENDED | $67,428 | $10,923 |
$65,221
1,502,931
kWh
|
$2,207 | ||
| TOTAL IMPLEMENTED | $28,320 | $10,423 |
$26,113
571,512
kWh
|
$2,207 | ||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Administrative Changes Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs