| Assessment Year | 1987 |
|---|---|
| Principal Product | PACKAGED SEAFOOD |
| NAICS |
n/a
|
| SIC | 2092: Prepared Fresh or Frozen Fish and Seafoods |
| Sales Range | $10 M to 50M |
| # of Employees | 50 |
| Plant Area |
n/a
|
| Annual Production | 11,200,000
lb
|
| Production Hrs. Annual | 8,736
hrs
|
| Location (State) | Oregon |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $93,594 | 1,832,943 |
kWh
|
$0.051 |
| Natural Gas | $34,818 | 5,780 |
MMBtu
|
$6.02 |
| Fuel Oil #2 | $3,334 | 952 |
MMBtu
|
$3.50 |
| TOTAL YEARLY COSTS | - | |||
| RECOMMENDED SAVINGS* | $18,687 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | $17,442 | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Fuel Oil #2 Savings | Administrative Changes Savings |
|---|---|---|---|---|---|---|---|
| 01 | 2.2621: Modify refrigeration system to operate at a lower pressure | $10,322 | - |
$10,322
202,227
kWh
|
- | - | |
| 02 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $377 | - |
$377
7,327
kWh
|
- | - | |
| 03 | 2.6232: Install set-back timers | $830 | $31 |
$560
10,844
kWh
|
- | $270 | |
| 04 | 2.1233: Analyze flue gas for proper air/fuel ratio | $890 | $300 | - |
$890
-
MMBtu
|
- | |
| 05 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $5,770 | $2,816 |
$2,781
54,220
kWh
|
- | $2,989 | |
| 06 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $246 | - |
$528
10,258
kWh
|
- | $(-282.0) | |
| 07 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $83 | - |
$757
14,947
kWh
|
- | $(-674.0) | |
| 08 | 2.4133: Use most efficient type of electric motors | $169 | $172 |
$169
3,224
kWh
|
- | - | |
| TOTAL RECOMMENDED | $18,687 | $3,319 |
$15,494
303,047
kWh
|
$890
-
MMBtu
|
$2,303 | ||
| TOTAL IMPLEMENTED | $17,442 | $3,116 |
$14,237
278,721
kWh
|
$890
-
MMBtu
|
$2,315 | ||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Fuel Oil #2 Savings | Administrative Changes Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs