| Assessment Year | 2026 |
|---|---|
| Principal Product | Steel, titanium, & aluminum specially treated parts for aircraft |
| NAICS | 332812: Metal Coating, Engraving (except Jewelry and Silverware), and Allied Services to Manufacturers |
| SIC | 3479: Coating, Engraving, and Allied Services, Not Elsewhere Classified |
| Sales Range | $10 M to 50M |
| # of Employees | 225 |
| Plant Area |
160,000
ft2
|
| Annual Production | 772,891
pieces
|
| Production Hrs. Annual | 7,644
hrs
|
| Location (State) | Kansas |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | ||
|---|---|---|---|---|---|
| Electricity Usage | $161,668 | 3,746,569 |
kWh
|
$0.043 | |
| Electricity Demand | $183,632 | 8,444 |
kW-mo/yr
|
$21.75 | |
| Natural Gas | $190,888 | 38,297 |
MMBtu
|
$4.98 | |
| Waste Disposal Costs | |||||
| Water Usage | $163,632 | 44,008 |
Tgal
|
$3.72 | |
| Water Disposal | $211,295 | 44,008 |
Tgal
|
$4.80 | |
| TOTAL YEARLY COSTS | $911,115 | ||||
| RECOMMENDED SAVINGS* | $153,947 |
See individual recommendations below
*Non-energy impacts included in savings.
|
|||
| IMPLEMENTED SAVINGS* | - | ||||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Water Usage Savings | Water Disposal Savings |
|---|---|---|---|---|---|---|---|---|---|
| 01 | 2.3134: Shift from daytime to nighttime operation | $16,078 | - | - |
$16,078
-
kW-mo/yr
|
- | - | - | |
| 02 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $12,656 | $19,265 |
$8,995
224,884
kWh
|
$3,661
-
kW-mo/yr
|
- | - | - | |
| 03 | 2.1224: Replace boiler | $29,600 | $140,000 | - | - |
$29,600
-
MMBtu
|
- | - | |
| 04 | 2.5194: Redesign process | $51,525 | $143,270 | - | - | - |
$24,574
-
Tgal
|
$26,951
-
Tgal
|
|
| 05 | 2.1133: Adjust burners for efficient operation | $1,716 | $1,300 | - | - |
$1,716
-
MMBtu
|
- | - | |
| 06 | 2.7261: Install timers and/or thermostats | $11,793 | $500 | - | - |
$11,793
-
MMBtu
|
- | - | |
| 07 | 2.9114: Use solar heat to make electricty | $30,579 | $511,000 |
$30,579
764,462
kWh
|
- | - | - | - | |
| TOTAL RECOMMENDED | $153,947 | $815,335 |
$39,574
989,346
kWh
|
$19,739
-
kW-mo/yr
|
$43,109
-
MMBtu
|
$24,574
-
Tgal
|
$26,951
-
Tgal
|
||
| TOTAL IMPLEMENTED | - | - | - | - | - | - | - | ||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Water Usage Savings | Water Disposal Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs