Assessment Year | 2021 |
---|---|
Principal Product | Aircraft parts |
NAICS | 336413: Other Aircraft Parts and Auxiliary Equipment Manufacturing |
SIC | 3728: Aircraft Parts and Auxiliary Equipment, Not Elsewhere Classified |
Sales Range | $1 M to 5M |
# of Employees | 40 |
Plant Area |
106,000
ft2
|
Annual Production | 664,633
lb
|
Production Hrs. Annual | 2,860
hrs
|
Location (State) | Kansas |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | ||
---|---|---|---|---|---|
Electricity Usage | $134,822 | 1,926,024 |
kWh
|
$0.070 | |
Electricity Demand | $135,840 | 13,112 |
kW-mo/yr
|
$10.36 | |
Electricity Fees | $758 | - |
|
- | |
Natural Gas | $29,857 | 4,483 |
MMBtu
|
$6.66 | |
Waste Disposal Costs | |||||
Water Usage | $7,565 | 705 |
Tgal
|
$10.73 | |
TOTAL YEARLY COSTS | $308,842 | ||||
RECOMMENDED SAVINGS* | $19,396 |
See individual recommendations below
*Non-energy impacts included in savings.
|
|||
IMPLEMENTED SAVINGS* | $16,040 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings |
---|---|---|---|---|---|---|---|
01 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $8,011 | $14,146 |
$5,918
84,546
kWh
|
$2,093
-
kW-mo/yr
|
- | |
02 | 2.6218: Turn off equipment when not in use | $3,431 | - |
$3,431
49,012
kWh
|
- | - | |
03 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $3,356 | $512 |
$3,356
47,947
kWh
|
- | - | |
04 | 2.4231: Reduce the pressure of compressed air to the minimum required | $527 | - |
$527
7,522
kWh
|
- | - | |
05 | 2.4221: Install compressor air intakes in coolest locations | $1,363 | $528 |
$841
12,012
kWh
|
$522
-
kW-mo/yr
|
- | |
06 | 2.6218: Turn off equipment when not in use | $1,380 | - |
$1,380
19,710
kWh
|
- | - | |
07 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $1,188 | $2,563 |
$1,188
16,972
kWh
|
- | - | |
08 | 2.7491: Insulate glazing, walls, ceilings, and roofs | $140 | $110 | - | - |
$140
-
MMBtu
|
|
TOTAL RECOMMENDED | $19,396 | $17,859 |
$16,641
237,721
kWh
|
$2,615
-
kW-mo/yr
|
$140
-
MMBtu
|
||
TOTAL IMPLEMENTED | $16,040 | $17,347 |
$13,285
189,774
kWh
|
$2,615
-
kW-mo/yr
|
$140
-
MMBtu
|
||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs