| Assessment Year | 2017 |
|---|---|
| Principal Product | Plastic products |
| NAICS | 326121: Unlaminated Plastics Profile Shape Manufacturing |
| SIC | 3089: Plastics Products, Not Elsewhere Classified |
| Sales Range | $10 M to 50M |
| # of Employees | 127 |
| Plant Area |
220,000
ft2
|
| Annual Production | 17,152,684
units
|
| Production Hrs. Annual | 6,240
hrs
|
| Location (State) | Oklahoma |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | ||
|---|---|---|---|---|---|
| Electricity Usage | $370,189 | 8,689,340 |
kWh
|
$0.043 | |
| Electricity Demand | $239,481 | 19,858 |
kW-mo/yr
|
$12.06 | |
| Natural Gas | $10,607 | 2,313 |
MMBtu
|
$4.59 | |
| Waste Disposal Costs | |||||
| Water Usage | $2,703 | 210 |
Tgal
|
$12.87 | |
| TOTAL YEARLY COSTS | $622,980 | ||||
| RECOMMENDED SAVINGS* | $91,596 |
See individual recommendations below
*Non-energy impacts included in savings.
|
|||
| IMPLEMENTED SAVINGS* | $55,636 | ||||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings |
|---|---|---|---|---|---|---|---|
| 01 | 2.2622: Replace existing chiller with high efficiency model | $31,812 | $180,000 |
$31,812
739,815
kWh
|
- | - | |
| 02 | 2.7211: Clean and maintain refrigerant condensers and towers | $8,586 | $3,840 |
$8,586
199,980
kWh
|
- | - | |
| 03 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $13,176 | $61,707 |
$8,559
199,037
kWh
|
$4,617
-
kW-mo/yr
|
- | |
| 04 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $17,185 | $3,480 |
$17,185
399,672
kWh
|
- | - | |
| 05 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $6,681 | $35,200 |
$6,681
155,392
kWh
|
- | - | |
| 06 | 3.1191: Change procedures / equipment / operating conditions | $12,094 | $22,000 |
$4,858
112,995
kWh
|
$7,236
-
kW-mo/yr
|
- | |
| 07 | 2.6232: Install set-back timers | $1,177 | $240 |
$178
4,133
kWh
|
- |
$1,000
-
MMBtu
|
|
| 08 | 2.6125: Keep equipment clean | $885 | $240 | - | - |
$885
-
MMBtu
|
|
| TOTAL RECOMMENDED | $91,596 | $306,707 |
$77,859
1,811,024
kWh
|
$11,853
-
kW-mo/yr
|
$1,885
-
MMBtu
|
||
| TOTAL IMPLEMENTED | $55,636 | $246,027 |
$49,135
1,142,965
kWh
|
$4,617
-
kW-mo/yr
|
$1,885
-
MMBtu
|
||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs