Assessment Year | 2015 |
---|---|
Principal Product | Commercial printing |
NAICS | 323111: Commercial Printing (except Screen and Books) |
SIC | 2754: Commercial Printing, Gravure |
Sales Range | $10 M to 50M |
# of Employees | 46 |
Plant Area |
65,000
ft2
|
Annual Production | 50,000,000
units
|
Production Hrs. Annual | 6,240
hrs
|
Location (State) | Oklahoma |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $124,169 | 2,194,080 |
kWh
|
$0.057 |
Electricity Demand | $45,311 | 6,364 |
kW-mo/yr
|
$7.12 |
Natural Gas | $42,048 | 8,504 |
MMBtu
|
$4.94 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $68,303 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | - |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Natural Gas Savings | Administrative Changes Savings |
---|---|---|---|---|---|---|---|---|---|
01 | 2.7241: Install outside air damper / economizer on hvac unit | $11,299 | $3,815 |
$11,299
198,235
kWh
|
- | - | - | - | |
02 | 2.7211: Clean and maintain refrigerant condensers and towers | $2,194 | - |
$1,939
34,024
kWh
|
$584
-
kW-mo/yr
|
- | - | $(-330.0) | |
03 | 2.6232: Install set-back timers | $2,270 | $1,550 |
$1,227
21,534
kWh
|
- | - |
$1,042
-
MMBtu
|
- | |
04 | 2.7496: Install partitions to reduce size of conditioned space | $820 | $3,450 |
$820
14,381
kWh
|
- | - | - | - | |
05 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $3,796 | $15,971 |
$3,113
54,610
kWh
|
$684
-
kW-mo/yr
|
- | - | - | |
06 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $1,190 | $5,218 |
$840
14,732
kWh
|
$350
-
kW-mo/yr
|
- | - | - | |
07 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $2,921 | $2,360 |
$2,605
45,702
kWh
|
$316
-
kW-mo/yr
|
- | - | - | |
08 | 2.7211: Clean and maintain refrigerant condensers and towers | $1,051 | - |
$2,131
37,389
kWh
|
- | - | - | $(-1,080.0) | |
09 | 2.2614: Use cooling tower or economizer to replace chiller cooling | $15,138 | $18,243 |
$14,969
262,609
kWh
|
$170
-
kW-mo/yr
|
- | - | - | |
10 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $3,980 | $1,500 |
$3,980
69,825
kWh
|
- | - | - | - | |
11 | 2.3212: Optimize plant power factor | $3,157 | $20,000 | - | - | $3,157 | - | - | |
12 | 2.8114: Change rate schedules or other changes in utility service | $20,000 | $65,000 | - | - | $20,000 | - | - | |
13 | 2.6218: Turn off equipment when not in use | $487 | $476 |
$487
8,551
kWh
|
- | - | - | - | |
TOTAL RECOMMENDED | $68,303 | $137,583 |
$43,410
761,592
kWh
|
$2,104
-
kW-mo/yr
|
$23,157 |
$1,042
-
MMBtu
|
$(-1,410.0) | ||
TOTAL IMPLEMENTED | - | - | - | - | - | - | - | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Natural Gas Savings | Administrative Changes Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs