Assessment Year 1989
Principal Product LADIES SPORTSWEAR
NAICS
n/a
SIC 2335: Women's, Misses', and Juniors' Dresses
Sales Range $5
M
to 10
M
# of Employees 164
Plant Area
n/a
Annual Production 400,000
pieces
Production Hrs. Annual 1,875
hrs
Location (State) Tennessee

Facility Energy Cost and Usage

Source Yearly Cost Usage
Electricity Usage $49,933 747,069
kWh
Natural Gas $14,780 3,857
MMBtu
TOTAL YEARLY COSTS -
RECOMMENDED SAVINGS* $7,369 *Non-energy impacts included in savings.
IMPLEMENTED SAVINGS* $4,926

Recommendations

# Description Yearly Savings* Imp'd Cost* Status Electricity Usage Savings Natural Gas Savings
01 2.1232: Keep boiler tubes clean $1,406 $320 - $1,406
-
MMBtu
02 2.2136: Install / repair insulation on steam lines $503 $447 - $503
-
MMBtu
03 2.1233: Analyze flue gas for proper air/fuel ratio $431 $225 - $431
-
MMBtu
04 2.2163: Use minimum steam operating pressure $384 - - $384
-
MMBtu
05 2.2511: Insulate bare equipment $223 $270 $79
1,172
kWh
$144
-
MMBtu
06 2.2153: Close off unneeded steam lines $118 $210 - $118
-
MMBtu
07 2.1233: Analyze flue gas for proper air/fuel ratio $95 $1,700 - $95
-
MMBtu
08 2.4231: Reduce the pressure of compressed air to the minimum required $334 $250 $334
4,982
kWh
-
09 2.4111: Utilize energy-efficient belts and other improved mechanisms $294 - $294
4,396
kWh
-
10 2.7142: Utilize higher efficiency lamps and/or ballasts $1,100 $616 $1,100
16,413
kWh
-
11 2.2122: Install / repair insulation on condensate lines $38 $30 - $38
-
MMBtu
12 2.6211: Conserve energy by efficient use of vending machines $157 $385 $157
2,345
kWh
-
13 2.8114: Change rate schedules or other changes in utility service $2,286 - $2,286
-
kWh
-
TOTAL RECOMMENDED $7,369 $4,453 $4,250
29,308
kWh
$3,119
-
MMBtu
TOTAL IMPLEMENTED $4,926 $4,068 $1,807
26,963
kWh
$3,119
-
MMBtu
Yearly Savings* Imp'd Cost* Electricity Usage Savings Natural Gas Savings
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs