Assessment Year | 2014 |
---|---|
Principal Product | Plastic Wares |
NAICS | 326199: All Other Plastics Product Manufacturing |
SIC | 3089: Plastics Products, Not Elsewhere Classified |
Sales Range | $100 M to 500M |
# of Employees | 130 |
Plant Area |
90,000
ft2
|
Annual Production | 17,500,000
pieces
|
Production Hrs. Annual | 7,488
hrs
|
Location (State) | Oklahoma |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $261,051 | 5,273,173 |
kWh
|
$0.050 |
Electricity Demand | $76,297 | 13,132 |
kW-mo/yr
|
$5.81 |
Natural Gas | $64,668 | 12,802 |
MMBtu
|
$5.05 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $66,267 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $3,955 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Natural Gas Savings |
---|---|---|---|---|---|---|---|---|
01 | 2.4221: Install compressor air intakes in coolest locations | $906 | $463 |
$906
18,129
kWh
|
- | - | - | |
02 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $1,972 | $1,750 |
$1,972
39,431
kWh
|
- | - | - | |
03 | 2.7135: Install occupancy sensors | $2,502 | $2,480 |
$2,502
50,045
kWh
|
- | - | - | |
04 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $445 | $2,048 |
$445
8,897
kWh
|
- | - | - | |
05 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $925 | $1,510 |
$792
15,836
kWh
|
$133
-
kW-mo/yr
|
- | - | |
06 | 2.7211: Clean and maintain refrigerant condensers and towers | $3,030 | $980 |
$2,333
46,656
kWh
|
$697
-
kW-mo/yr
|
- | - | |
07 | 2.7261: Install timers and/or thermostats | $4,226 | $2,681 |
$2,948
58,958
kWh
|
- | - |
$1,278
-
MMBtu
|
|
08 | 2.7231: Use radiant heater for spot heating | $7,584 | $15,000 | - | - | - |
$7,584
-
MMBtu
|
|
09 | 2.3212: Optimize plant power factor | $8,198 | $18,876 | - | - | $8,198 | - | |
10 | 2.2437: Recover waste heat from equipment | $12,481 | $30,000 | - | - | - |
$12,481
-
MMBtu
|
|
11 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $221 | $1,083 |
$164
3,272
kWh
|
$57
-
kW-mo/yr
|
- | - | |
12 | 2.7241: Install outside air damper / economizer on hvac unit | $23,778 | $19,100 |
$23,778
475,551
kWh
|
- | - | - | |
TOTAL RECOMMENDED | $66,267 | $95,971 |
$35,839
716,775
kWh
|
$887
-
kW-mo/yr
|
$8,198 |
$21,343
-
MMBtu
|
||
TOTAL IMPLEMENTED | $3,955 | $2,490 |
$3,125
62,492
kWh
|
$830
-
kW-mo/yr
|
- | - | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Natural Gas Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs