Assessment Year | 2013 |
---|---|
Principal Product | Traffic Signal Hardware, Utility Products, Decorative Outdoor Lighting |
NAICS | 332510: Hardware Manufacturing |
SIC | 3499: Fabricated Metal Products, Not Elsewhere Classified |
Sales Range | $10 M to 50M |
# of Employees | 160 |
Plant Area |
120,000
ft2
|
Annual Production | 633,336
units
|
Production Hrs. Annual | 2,288
hrs
|
Location (State) | Oklahoma |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $86,563 | 1,074,860 |
kWh
|
$0.081 |
Electricity Demand | $19,778 | 2,258 |
kW-mo/yr
|
$8.76 |
Natural Gas | $30,702 | 6,758 |
MMBtu
|
$4.54 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $25,425 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $9,117 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings |
---|---|---|---|---|---|---|---|
01 | 2.7241: Install outside air damper / economizer on hvac unit | $8,579 | $6,400 |
$8,579
153,204
kWh
|
- | - | |
02 | 2.7211: Clean and maintain refrigerant condensers and towers | $1,208 | $3,900 |
$621
10,372
kWh
|
$587
-
kW-mo/yr
|
- | |
03 | 2.6232: Install set-back timers | $3,386 | $894 |
$1,181
19,719
kWh
|
- |
$2,205
-
MMBtu
|
|
04 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $5,837 | $21,300 |
$3,598
64,241
kWh
|
$2,239
-
kW-mo/yr
|
- | |
05 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $1,294 | $2,444 |
$958
9,576
kWh
|
$336
-
kW-mo/yr
|
- | |
06 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $1,712 | $500 |
$1,712
24,223
kWh
|
- | - | |
07 | 2.2437: Recover waste heat from equipment | $747 | $1,909 | - | - |
$747
-
MMBtu
|
|
08 | 2.4322: Use or replace with energy efficient substitutes | $346 | $701 |
$346
3,459
kWh
|
- | - | |
09 | 2.4322: Use or replace with energy efficient substitutes | $2,228 | $4,333 |
$2,228
22,283
kWh
|
- | - | |
10 | 2.4322: Use or replace with energy efficient substitutes | $74 | - |
$74
1,325
kWh
|
- | - | |
11 | 2.2511: Insulate bare equipment | $15 | $44 | - | - |
$15
-
MMBtu
|
|
TOTAL RECOMMENDED | $25,425 | $42,425 |
$19,296
308,402
kWh
|
$3,162
-
kW-mo/yr
|
$2,967
-
MMBtu
|
||
TOTAL IMPLEMENTED | $9,117 | $26,445 |
$6,276
102,295
kWh
|
$2,826
-
kW-mo/yr
|
$15
-
MMBtu
|
||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings |