Assessment Year | 2013 |
---|---|
Principal Product | Industrial and Automotive Seals & Gaskets |
NAICS | 336350: Motor Vehicle Transmission and Power Train Parts Manufacturing |
SIC | 3714: Motor Vehicle Parts and Accessories |
Sales Range | $50 M to 100M |
# of Employees | 235 |
Plant Area |
89,000
ft2
|
Annual Production | 30,000,000
pieces
|
Production Hrs. Annual | 8,760
hrs
|
Location (State) | Oklahoma |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $418,864 | 11,046,000 |
kWh
|
$0.038 |
Electricity Demand | $213,109 | 24,665 |
kW-mo/yr
|
$8.64 |
Electricity Fees | $(-126,654.2) | - |
|
- |
Natural Gas | $16,443 | 5,447 |
MMBtu
|
$3.02 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $168,556 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $6,427 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings |
---|---|---|---|---|---|---|---|
01 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $6,427 | $1,250 |
$6,427
169,140
kWh
|
- | - | |
02 | 2.4221: Install compressor air intakes in coolest locations | $1,478 | $1,026 |
$1,478
38,882
kWh
|
- | - | |
03 | 2.2437: Recover waste heat from equipment | $1,425 | $1,378 | - | - |
$1,425
-
MMBtu
|
|
04 | 2.7242: Change zone reheat coils to variable air volume boxes | $834 | $3,110 |
$606
15,959
kWh
|
$228
-
kW-mo/yr
|
- | |
05 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $2,689 | $13,383 |
$2,047
53,856
kWh
|
$642
-
kW-mo/yr
|
- | |
06 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $377 | $9,558 |
$377
9,914
kWh
|
- | - | |
07 | 2.7232: Replace existing hvac unit with high efficiency model | $22,838 | $54,080 |
$12,840
337,891
kWh
|
$9,998
-
kW-mo/yr
|
- | |
08 | 2.7241: Install outside air damper / economizer on hvac unit | $960 | $1,500 |
$960
25,272
kWh
|
- | - | |
09 | 2.7211: Clean and maintain refrigerant condensers and towers | $12,086 | $2,710 |
$8,699
228,916
kWh
|
$3,387
-
kW-mo/yr
|
- | |
10 | 2.2628: Utilize a less expensive cooling method | $53,906 | $518,400 |
$38,801
1,021,066
kWh
|
$15,106
-
kW-mo/yr
|
- | |
11 | 2.4322: Use or replace with energy efficient substitutes | $65,536 | $250,000 |
$43,141
1,135,296
kWh
|
$22,395
-
kW-mo/yr
|
- | |
TOTAL RECOMMENDED | $168,556 | $856,395 |
$115,375
3,036,192
kWh
|
$51,756
-
kW-mo/yr
|
$1,425
-
MMBtu
|
||
TOTAL IMPLEMENTED | $6,427 | $1,250 |
$6,427
169,140
kWh
|
- | - | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs