| Assessment Year | 2012 |
|---|---|
| Principal Product | Hardwood Flooring |
| NAICS | 321918: Other Millwork (including Flooring) |
| SIC | 2426: Hardwood Dimension and Flooring Mills |
| Sales Range | $10 M to 50M |
| # of Employees | 300 |
| Plant Area |
135,000
ft2
|
| Annual Production | 1,500
thousand feet
|
| Production Hrs. Annual | 6,240
hrs
|
| Location (State) | Arkansas |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $1,047,458 | 21,619,560 |
kWh
|
$0.048 |
| Electricity Demand | $383,093 | 47,129 |
kW-mo/yr
|
$8.13 |
| Natural Gas | $22,567 | 2,902 |
MMBtu
|
$7.78 |
| TOTAL YEARLY COSTS | - | |||
| RECOMMENDED SAVINGS* | $320,900 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | $47,500 | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Wood Savings |
|---|---|---|---|---|---|---|---|---|
| 01 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $1,500 | $1,700 |
$1,220
25,100
kWh
|
$280
-
kW-mo/yr
|
- | - | |
| 02 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $11,200 | $27,500 |
$8,500
175,500
kWh
|
$2,700
-
kW-mo/yr
|
- | - | |
| 03 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $2,400 | $10,000 |
$1,800
36,900
kWh
|
$600
-
kW-mo/yr
|
- | - | |
| 04 | 2.4224: Upgrade controls on compressors | $28,900 | $15,100 |
$15,900
332,000
kWh
|
$13,000
-
kW-mo/yr
|
- | - | |
| 05 | 2.1233: Analyze flue gas for proper air/fuel ratio | $9,000 | $500 | - | - | - |
$9,000
-
MMBtu
|
|
| 06 | 2.1321: Replace fossil fuel equipment with electrical equipment | $7,200 | $1,000 |
$(-9,800.0)
(-202,000)
kWh
|
$(-5,300.0)
-
kW-mo/yr
|
$22,300
-
MMBtu
|
- | |
| 07 | 2.3414: Burn waste to produce steam to drive a steam turbine generator set and use steam exhaust for heat | $248,000 | $675,000 |
$248,000
4,400,000
kWh
|
- | - | - | |
| 08 | 2.4131: Size electric motors for peak operating efficiency | $12,700 | $13,000 |
$12,700
187,500
kWh
|
- | - | - | |
| TOTAL RECOMMENDED | $320,900 | $743,800 |
$278,320
4,955,000
kWh
|
$11,280
-
kW-mo/yr
|
$22,300
-
MMBtu
|
$9,000
-
MMBtu
|
||
| TOTAL IMPLEMENTED | $47,500 | $26,600 |
$7,900
166,900
kWh
|
$8,300
-
kW-mo/yr
|
$22,300
-
MMBtu
|
$9,000
-
MMBtu
|
||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Wood Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs