| Assessment Year | 2010 |
|---|---|
| Principal Product | Refrigeration Units |
| NAICS | 333415: Air-Conditioning and Warm Air Heating Equipment and Commercial and Industrial Refrigeration Equipmen |
| SIC | 3585: Air-Conditioning and Warm Air Heating Equipment and Commercial and Industrial Refrigeration Equipment |
| Sales Range | $10 M to 50M |
| # of Employees | 240 |
| Plant Area |
220,000
ft2
|
| Annual Production | 14,000
pieces
|
| Production Hrs. Annual | 4,680
hrs
|
| Location (State) | Oklahoma |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $186,802 | 3,045,312 |
kWh
|
$0.061 |
| Natural Gas | $54,522 | 7,964 |
MMBtu
|
$6.85 |
| TOTAL YEARLY COSTS | - | |||
| RECOMMENDED SAVINGS* | $37,663 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | $7,326 | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Fees Savings | Natural Gas Savings |
|---|---|---|---|---|---|---|---|
| 01 | 2.3212: Optimize plant power factor | $16,798 | $29,735 | - | $16,798 | - | |
| 02 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $3,028 | $14,578 |
$3,028
49,401
kWh
|
- | - | |
| 03 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $1,129 | $5,526 |
$1,129
18,421
kWh
|
- | - | |
| 04 | 2.2437: Recover waste heat from equipment | $2,660 | $1,378 | - | - |
$2,660
-
MMBtu
|
|
| 05 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $2,383 | $500 |
$2,383
38,877
kWh
|
- | - | |
| 06 | 2.4221: Install compressor air intakes in coolest locations | $851 | $217 |
$851
13,885
kWh
|
- | - | |
| 07 | 2.7232: Replace existing hvac unit with high efficiency model | $10,028 | $23,000 | - | - |
$10,028
-
MMBtu
|
|
| 08 | 2.7224: Reduce space conditioning during non-working hours | $786 | $1,850 | - | - |
$786
-
MMBtu
|
|
| TOTAL RECOMMENDED | $37,663 | $76,784 |
$7,391
120,584
kWh
|
$16,798 |
$13,474
-
MMBtu
|
||
| TOTAL IMPLEMENTED | $7,326 | $22,454 |
$6,540
106,699
kWh
|
- |
$786
-
MMBtu
|
||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Fees Savings | Natural Gas Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs