| Assessment Year | 2010 |
|---|---|
| Principal Product | Batteries |
| NAICS | 335911: Storage Battery Manufacturing |
| SIC | 3692: Primary Batteries, Dry and Wet |
| Sales Range | $50 M to 100M |
| # of Employees | 206 |
| Plant Area |
150,000
ft2
|
| Annual Production | 421,000
pieces
|
| Production Hrs. Annual | 7,488
hrs
|
| Location (State) | Arkansas |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $1,094,155 | 21,945,600 |
kWh
|
$0.050 |
| Natural Gas | $495,376 | 72,602 |
MMBtu
|
$6.82 |
| TOTAL YEARLY COSTS | - | |||
| RECOMMENDED SAVINGS* | $124,517 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | $57,362 | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Natural Gas Savings |
|---|---|---|---|---|---|---|
| 01 | 2.2136: Install / repair insulation on steam lines | $285 | $451 | - |
$285
-
MMBtu
|
|
| 02 | 2.1121: Use insulation in furnaces to facilitate heating / cooling | $29,667 | $2,587 | - |
$29,667
-
MMBtu
|
|
| 03 | 2.1121: Use insulation in furnaces to facilitate heating / cooling | $1,568 | $1,078 | - |
$1,568
-
MMBtu
|
|
| 04 | 2.1135: Repair furnaces and oven doors so that they seal efficiently | $3,625 | $1,176 | - |
$3,625
-
MMBtu
|
|
| 05 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $1,103 | $5,543 |
$1,103
22,117
kWh
|
- | |
| 06 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $2,350 | $8,818 |
$2,350
47,129
kWh
|
- | |
| 07 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $35,265 | $98,109 |
$35,265
707,317
kWh
|
- | |
| 08 | 2.4221: Install compressor air intakes in coolest locations | $441 | $1,170 |
$441
8,833
kWh
|
- | |
| 09 | 2.4231: Reduce the pressure of compressed air to the minimum required | $5,877 | - |
$5,877
117,540
kWh
|
- | |
| 10 | 2.7232: Replace existing hvac unit with high efficiency model | $15,837 | $12,000 |
$15,837
303,085
kWh
|
- | |
| 11 | 2.7232: Replace existing hvac unit with high efficiency model | $6,106 | $101,906 |
$6,106
122,129
kWh
|
- | |
| 12 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $22,393 | $7,656 |
$22,393
447,861
kWh
|
- | |
| TOTAL RECOMMENDED | $124,517 | $240,494 |
$89,372
1,776,011
kWh
|
$35,145
-
MMBtu
|
||
| TOTAL IMPLEMENTED | $57,362 | $120,554 |
$53,452
1,057,531
kWh
|
$3,910
-
MMBtu
|
||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Natural Gas Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs