Assessment Year | 2008 |
---|---|
Principal Product | Electric Motors and Drives |
NAICS | 335312: Motor and Generator Manufacturing |
SIC | 3621: Motors and Generators |
Sales Range | $10 M to 50M |
# of Employees | 296 |
Plant Area |
160,000
ft2
|
Annual Production | 220,000
units
|
Production Hrs. Annual | 6,240
hrs
|
Location (State) | Arkansas |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $475,169 | 6,132,000 |
kWh
|
$0.077 |
Natural Gas | $71,845 | 6,514 |
MMBtu
|
$11.03 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $41,684 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $31,776 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Natural Gas Savings |
---|---|---|---|---|---|---|
01 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $7,297 | - |
$7,297
124,100
kWh
|
- | |
02 | 2.4231: Reduce the pressure of compressed air to the minimum required | $2,597 | - |
$2,597
39,713
kWh
|
- | |
03 | 2.4221: Install compressor air intakes in coolest locations | $669 | $1,056 |
$669
10,234
kWh
|
- | |
04 | 2.2437: Recover waste heat from equipment | $8,014 | $5,534 | - |
$8,014
-
MMBtu
|
|
05 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $4,686 | $17,885 |
$4,686
56,010
kWh
|
- | |
06 | 2.7243: Improve air circulation with destratification fans / other methods | $1,894 | $1,346 |
$1,894
28,968
kWh
|
- | |
07 | 2.6218: Turn off equipment when not in use | $16,527 | - |
$16,527
252,703
kWh
|
- | |
TOTAL RECOMMENDED | $41,684 | $25,821 |
$33,670
511,728
kWh
|
$8,014
-
MMBtu
|
||
TOTAL IMPLEMENTED | $31,776 | $18,941 |
$31,776
482,760
kWh
|
- | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Natural Gas Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs