Assessment Year 2006
Principal Product Automotive Softgoods
NAICS 326111: Plastics Bag and Pouch Manufacturing
SIC 3083: Laminated Plastics Plate, Sheet, and Profile Shapes
Sales Range $10
M
to 50
M
# of Employees 160
Plant Area 125,000
ft2
Annual Production 190,000
pieces
Production Hrs. Annual 2,600
hrs
Location (State) Oklahoma

Facility Energy Cost and Usage

Source Yearly Cost Usage
Electricity Usage $58,195 1,442,480
kWh
Electricity Demand $52,862 6,024
kW-mo/yr
Natural Gas $13,532 1,317
MMBtu
TOTAL YEARLY COSTS -
RECOMMENDED SAVINGS* $28,073 *Non-energy impacts included in savings.
IMPLEMENTED SAVINGS* $14,476

Recommendations

# Description Yearly Savings* Imp'd Cost* Status Electricity Usage Savings Electricity Demand Savings Natural Gas Savings Personnel Changes Savings
01 2.7221: Lower temperature during the winter season and vice-versa $5,766 $10,375 $2,815
34,293
kWh
- $2,951
-
MMBtu
-
02 2.3131: Reschedule plant operations or reduce load to avoid peaks $4,201 $5,750 - $4,201
-
kW-mo/yr
- -
03 2.4234: Cool compressor air intake with heat exchanger $266 $521 $122
3,016
kWh
$144
-
kW-mo/yr
- -
04 2.4226: Use / purchase optimum sized compressor $2,193 $40 $1,017
25,176
kWh
$1,176
-
kW-mo/yr
- -
05 2.4231: Reduce the pressure of compressed air to the minimum required $407 $1,300 $188
4,655
kWh
$219
-
kW-mo/yr
- -
06 2.7232: Replace existing hvac unit with high efficiency model $2,157 $15,330 - - $1,357
-
MMBtu
$800
07 2.7135: Install occupancy sensors $1,066 $1,600 $1,066
13,957
kWh
- - -
08 2.7142: Utilize higher efficiency lamps and/or ballasts $10,222 $67,616 $7,847
103,664
kWh
- - $2,375
09 2.7142: Utilize higher efficiency lamps and/or ballasts $1,795 $8,054 $1,613
21,108
kWh
- - $182
TOTAL RECOMMENDED $28,073 $110,586 $14,668
205,869
kWh
$5,740
-
kW-mo/yr
$4,308
-
MMBtu
$3,357
TOTAL IMPLEMENTED $14,476 $76,231 $10,599
152,964
kWh
$1,320
-
kW-mo/yr
- $2,557
Yearly Savings* Imp'd Cost* Electricity Usage Savings Electricity Demand Savings Natural Gas Savings Personnel Changes Savings
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs