| Assessment Year | 1994 |
|---|---|
| Principal Product | Fuel filter cartridges |
| NAICS |
n/a
|
| SIC | 3569: General Industrial Machinery and Equipment, Not Elsewhere |
| Sales Range | $10 M to 50M |
| # of Employees | 60 |
| Plant Area |
67,500
ft2
|
| Annual Production | 360,000
pieces
|
| Production Hrs. Annual | 5,200
hrs
|
| Location (State) | Oklahoma |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $78,967 | 1,256,448 |
kWh
|
$0.063 |
| Natural Gas | $49,977 | 12,534 |
MMBtu
|
$3.99 |
| TOTAL YEARLY COSTS | - | |||
| RECOMMENDED SAVINGS* | $14,796 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | $12,737 | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Natural Gas Savings |
|---|---|---|---|---|---|---|
| 01 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $11,592 | $19,151 |
$11,592
197,538
kWh
|
- | |
| 02 | 2.6232: Install set-back timers | $2,059 | $1,200 |
$2,059
91,442
kWh
|
- | |
| 03 | 2.2136: Install / repair insulation on steam lines | $724 | $1,524 | - |
$724
-
MMBtu
|
|
| 04 | 2.7224: Reduce space conditioning during non-working hours | $342 | - | - |
$342
-
MMBtu
|
|
| 05 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $79 | $395 |
$79
2,345
kWh
|
- | |
| TOTAL RECOMMENDED | $14,796 | $22,270 |
$13,730
291,325
kWh
|
$1,066
-
MMBtu
|
||
| TOTAL IMPLEMENTED | $12,737 | $21,070 |
$11,671
199,883
kWh
|
$1,066
-
MMBtu
|
||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs