Assessment Year | 1986 |
---|---|
Principal Product | ROTARY DRILL BITS |
NAICS |
n/a
|
SIC | 3533: Oil and Gas Field Machinery and Equipment |
Sales Range | $10 M to 50M |
# of Employees | 320 |
Plant Area |
n/a
|
Annual Production | 43,800
pieces
|
Production Hrs. Annual | 8,736
hrs
|
Location (State) | Oklahoma |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $269,817 | 4,548,066 |
kWh
|
$0.059 |
Natural Gas | $107,183 | 29,660 |
MMBtu
|
$3.61 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $55,721 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $2,273 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Natural Gas Savings | Administrative Changes Savings |
---|---|---|---|---|---|---|---|
01 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $791 | - |
$1,291
33,998
kWh
|
- | $(-500.0) | |
02 | 2.6232: Install set-back timers | $1,482 | $845 |
$1,482
38,980
kWh
|
- | - | |
03 | 2.2414: Use waste heat from hot flue gases to preheat | $13,118 | $36,015 | - |
$13,118
-
MMBtu
|
- | |
04 | 2.2425: Use flue gases to heat process or service water | $6,158 | $5,270 | - |
$6,158
-
MMBtu
|
- | |
05 | 3.4115: Recover and reuse cooling water | $34,172 | $33,600 |
$4,097
107,562
kWh
|
- | $30,075 | |
TOTAL RECOMMENDED | $55,721 | $75,730 |
$6,870
180,540
kWh
|
$19,276
-
MMBtu
|
$29,575 | ||
TOTAL IMPLEMENTED | $2,273 | $845 |
$2,773
72,978
kWh
|
- | $(-500.0) |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs