Assessment Year 1983
Principal Product ICE CREAM AND MILK
NAICS
n/a
SIC 2026: Fluid Milk
Sales Range $10
M
to 50
M
# of Employees 200
Plant Area
n/a
Annual Production 131,000
Tgal
Production Hrs. Annual 5,775
hrs
Location (State) Oklahoma

Facility Energy Cost and Usage

Source Yearly Cost Usage
Electricity Usage $155,094 4,140,094
kWh
Natural Gas $108,065 35,746
MMBtu
TOTAL YEARLY COSTS -
RECOMMENDED SAVINGS* $85,647 *Non-energy impacts included in savings.
IMPLEMENTED SAVINGS* $59,590

Recommendations

# Description Yearly Savings* Imp'd Cost* Status Electricity Usage Savings Natural Gas Savings
01 2.7261: Install timers and/or thermostats $433 $759 - $433
-
MMBtu
02 2.2414: Use waste heat from hot flue gases to preheat $5,050 $8,000 - $5,050
-
MMBtu
03 2.2437: Recover waste heat from equipment $1,010 $423 - $1,010
-
MMBtu
04 2.7226: Use computer programs to optimize hvac performance $2,821 $3,032 $2,821
82,943
kWh
-
05 2.1233: Analyze flue gas for proper air/fuel ratio $5,161 $695 - $5,161
-
MMBtu
06 2.7142: Utilize higher efficiency lamps and/or ballasts $1,873 $4,897 $1,873
48,359
kWh
-
07 2.7142: Utilize higher efficiency lamps and/or ballasts $643 $1,765 $643
17,292
kWh
-
08 2.7142: Utilize higher efficiency lamps and/or ballasts $333 $1,117 $333
11,137
kWh
-
09 2.4133: Use most efficient type of electric motors $2,659 $490 $2,659
75,029
kWh
-
10 2.4133: Use most efficient type of electric motors $4,063 $270 - $4,063
-
MMBtu
11 2.2447: Heat water with exhaust heat $54,540 $36,000 - $54,540
-
MMBtu
12 2.8114: Change rate schedules or other changes in utility service $6,511 $27,000 $6,511
-
kWh
-
13 2.1131: Repair faulty insulation in furnaces, boilers, etc $471 $477 - $471
-
MMBtu
14 2.2122: Install / repair insulation on condensate lines $79 $136 - $79
-
MMBtu
TOTAL RECOMMENDED $85,647 $85,061 $14,840
234,760
kWh
$70,807
-
MMBtu
TOTAL IMPLEMENTED $59,590 $44,000 - $59,590
-
MMBtu
Yearly Savings* Imp'd Cost* Electricity Usage Savings Natural Gas Savings
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs