| Assessment Year | 1982 |
|---|---|
| Principal Product | INJECTION-MOLDED PLASTIC |
| NAICS |
n/a
|
| SIC | 3089: Plastics Products, Not Elsewhere Classified |
| Sales Range | $1 M to 5M |
| # of Employees | 25 |
| Plant Area |
n/a
|
| Annual Production | 0
units
|
| Production Hrs. Annual | 4,000
hrs
|
| Location (State) | Oklahoma |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $39,179 | 785,463 |
kWh
|
$0.050 |
| Natural Gas | $1,550 | 457 |
MMBtu
|
$3.39 |
| TOTAL YEARLY COSTS | - | |||
| RECOMMENDED SAVINGS* | $12,244 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | $1,042 | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Natural Gas Savings |
|---|---|---|---|---|---|---|
| 01 | 2.6212: Turn off equipment during breaks, reduce operating time | $2,410 | $9,010 |
$2,410
87,046
kWh
|
- | |
| 02 | 2.6212: Turn off equipment during breaks, reduce operating time | $973 | $633 |
$973
35,170
kWh
|
- | |
| 03 | 2.3191: Use demand controller or load shedder | $718 | $433 |
$718
-
kWh
|
- | |
| 04 | 2.6212: Turn off equipment during breaks, reduce operating time | $1,042 | - |
$1,042
37,808
kWh
|
- | |
| 05 | 2.3212: Optimize plant power factor | $1,504 | $1,520 |
$1,504
-
kWh
|
- | |
| 06 | 2.4322: Use or replace with energy efficient substitutes | $56 | $114 |
$56
2,052
kWh
|
- | |
| 07 | 2.7226: Use computer programs to optimize hvac performance | $5,173 | $24,000 |
$5,173
186,987
kWh
|
- | |
| 08 | 2.7261: Install timers and/or thermostats | $69 | $296 | - |
$69
-
MMBtu
|
|
| 09 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $263 | $95 |
$263
7,327
kWh
|
- | |
| 10 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $36 | $38 |
$36
879
kWh
|
- | |
| TOTAL RECOMMENDED | $12,244 | $36,139 |
$12,175
357,269
kWh
|
$69
-
MMBtu
|
||
| TOTAL IMPLEMENTED | $1,042 | $929 |
$973
35,170
kWh
|
$69
-
MMBtu
|
||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Natural Gas Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs