| Assessment Year | 2000 |
|---|---|
| Principal Product | Glass Containers |
| NAICS |
n/a
|
| SIC | 3221: Glass Containers |
| Sales Range | $10 M to 50M |
| # of Employees | 137 |
| Plant Area |
33,000
ft2
|
| Annual Production | 0
units
|
| Production Hrs. Annual | 8,232
hrs
|
| Location (State) | Virginia |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $81,385 | 2,604,631 |
kWh
|
$0.031 |
| Electricity Demand | $38,626 | 4,399 |
kW-mo/yr
|
$8.78 |
| Electricity Fees | $2,795 | - |
|
- |
| Natural Gas | $151,877 | 28,147 |
MMBtu
|
$5.40 |
| TOTAL YEARLY COSTS | - | |||
| RECOMMENDED SAVINGS* | $8,133 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | $6,001 | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings |
|---|---|---|---|---|---|---|
| 01 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $5,359 | $5,892 |
$3,587
114,889
kWh
|
$1,772
-
kW-mo/yr
|
|
| 02 | 2.7261: Install timers and/or thermostats | $1,337 | $115 |
$1,337
36,049
kWh
|
- | |
| 03 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $642 | $726 |
$456
7,034
kWh
|
$186
-
kW-mo/yr
|
|
| 04 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $795 | $1,000 |
$795
25,498
kWh
|
- | |
| TOTAL RECOMMENDED | $8,133 | $7,733 |
$6,175
183,470
kWh
|
$1,958
-
kW-mo/yr
|
||
| TOTAL IMPLEMENTED | $6,001 | $6,618 |
$4,043
121,923
kWh
|
$1,958
-
kW-mo/yr
|
||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs