Assessment Year | 1995 |
---|---|
Principal Product | Gaskets, Packing and Sealing Devices |
NAICS |
n/a
|
SIC | 3053: Gaskets, Packing, and Sealing Devices |
Sales Range | $10 M to 50M |
# of Employees | 325 |
Plant Area |
37,500
ft2
|
Annual Production | 11,651,000
pieces
|
Production Hrs. Annual | 8,400
hrs
|
Location (State) | Virginia |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $309,331 | 6,211,606 |
kWh
|
$0.050 |
Natural Gas | $6,863 | 1,081 |
MMBtu
|
$6.35 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $86,730 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $68,893 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings |
---|---|---|---|---|---|
01 | 2.2612: Use cooling tower water instead of refrigeration | $41,731 | $48,000 |
$41,731
890,387
kWh
|
|
02 | 2.4133: Use most efficient type of electric motors | $15,270 | $11,420 |
$15,270
306,565
kWh
|
|
03 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $403 | $118 |
$403
8,206
kWh
|
|
04 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $18,019 | $6,600 |
$18,019
361,958
kWh
|
|
05 | 2.4221: Install compressor air intakes in coolest locations | $890 | $500 |
$890
17,878
kWh
|
|
06 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $8,253 | $14,228 |
$8,253
165,885
kWh
|
|
07 | 2.7135: Install occupancy sensors | $2,164 | $2,084 |
$2,164
43,376
kWh
|
|
TOTAL RECOMMENDED | $86,730 | $82,950 |
$86,730
1,794,255
kWh
|
||
TOTAL IMPLEMENTED | $68,893 | $69,328 |
$68,893
1,436,108
kWh
|
||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs