| Assessment Year | 2000 |
|---|---|
| Principal Product | industrial inorganic chemicals |
| NAICS |
n/a
|
| SIC | 2819: Industrial Inorganic Chemicals, Not Elsewhere Classified |
| Sales Range | $10 M to 50M |
| # of Employees | 114 |
| Plant Area |
94,500
ft2
|
| Annual Production | 250,000,000
lb
|
| Production Hrs. Annual | 8,760
hrs
|
| Location (State) | Nevada |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $854,367 | 23,323,000 |
kWh
|
$0.037 |
| Electricity Demand | $137,484 | 36,528 |
kW-mo/yr
|
$3.76 |
| Electricity Fees | $3,244 | - |
|
- |
| Natural Gas | $2,302,564 | 613,139 |
MMBtu
|
$3.76 |
| TOTAL YEARLY COSTS | - | |||
| RECOMMENDED SAVINGS* | $349,824 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | - | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Personnel Changes Savings | Water Consumption Savings |
|---|---|---|---|---|---|---|---|---|---|
| 01 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $95,346 | $200 | n/a |
$83,592
2,281,946
kWh
|
$11,754
-
kW-mo/yr
|
- | - | - |
| 02 | 2.1113: Reduce combustion air flow to optimum | $75,664 | $100 | n/a | - | - |
$75,664
-
MMBtu
|
- | - |
| 03 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $21,258 | - | n/a |
$18,637
403,283
kWh
|
$2,621
-
kW-mo/yr
|
- | - | - |
| 04 | 2.4221: Install compressor air intakes in coolest locations | $4,704 | $150 | n/a |
$4,203
114,596
kWh
|
$501
-
kW-mo/yr
|
- | - | - |
| 05 | 4.426: Modify workload | $8,134 | - | n/a | - | - | - | $8,134 | - |
| 06 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $137,083 | $45,279 | n/a |
$187
2,931
kWh
|
- | - | $136,896 | - |
| 07 | 3.4151: Minimize water usage | $6,651 | $432 | n/a | - | - | - | - |
$6,651
-
Tgal
|
| 08 | 3.4154: Eliminate leaks in water lines and valves | $984 | $100 | n/a | - | - | - | - |
$984
-
Tgal
|
| TOTAL RECOMMENDED | $349,824 | $46,261 |
$106,619
2,802,756
kWh
|
$14,876
-
kW-mo/yr
|
$75,664
-
MMBtu
|
$145,030 |
$7,635
-
Tgal
|
||
| TOTAL IMPLEMENTED | - | - | - | - | - | - | - | ||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Personnel Changes Savings | Water Consumption Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs