Assessment Year | 2000 |
---|---|
Principal Product | ball and roller bearings |
NAICS |
n/a
|
SIC | 3562: Ball and Roller Bearings |
Sales Range | $10 M to 50M |
# of Employees | 26 |
Plant Area |
n/a
|
Annual Production | 100,000
pieces
|
Production Hrs. Annual | 2,125
hrs
|
Location (State) | Nevada |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $26,685 | 639,457 |
kWh
|
$0.042 |
Electricity Demand | $17,980 | 1,937 |
kW-mo/yr
|
$9.28 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $11,405 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $1,207 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings |
---|---|---|---|---|---|---|---|
01 | 2.1311: Replace electrically-operated equipment with fossil fuel equipment | $10,198 | $375 |
$6,580
157,680
kWh
|
$4,009
-
kW-mo/yr
|
$(-391.0)
-
MMBtu
|
|
02 | 2.4226: Use / purchase optimum sized compressor | $1,047 | $4,500 |
$74
21,594
kWh
|
$973
-
kW-mo/yr
|
- | |
03 | 2.4133: Use most efficient type of electric motors | $160 | $297 |
$66
1,583
kWh
|
$94
-
kW-mo/yr
|
- | |
TOTAL RECOMMENDED | $11,405 | $5,172 |
$6,720
180,857
kWh
|
$5,076
-
kW-mo/yr
|
$(-391.0)
-
MMBtu
|
||
TOTAL IMPLEMENTED | $1,207 | $4,797 |
$140
23,177
kWh
|
$1,067
-
kW-mo/yr
|
- |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs