Assessment Year | 2000 |
---|---|
Principal Product | Commercial Printing |
NAICS |
n/a
|
SIC | 2752: Commercial Printing, Lithographic |
Sales Range | $10 M to 50M |
# of Employees | 180 |
Plant Area |
n/a
|
Annual Production | 5,100
ton
|
Production Hrs. Annual | 8,760
hrs
|
Location (State) | California |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $202,620 | 2,240,621 |
kWh
|
$0.090 |
Electricity Demand | $11,521 | 839 |
kW-mo/yr
|
$13.73 |
Electricity Fees | $(-16,865.0) | - |
|
- |
Natural Gas | $17,849 | 2,693 |
MMBtu
|
$6.63 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $34,379 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | - |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Personnel Changes Savings |
---|---|---|---|---|---|---|---|---|
01 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $700 | $100 | n/a |
$686
7,327
kWh
|
- | $14 | - |
02 | 2.6231: Utilize controls to operate equipment only when needed | $1,139 | $370 | n/a |
$1,262
13,189
kWh
|
- | $(-123.0) | - |
03 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $2,943 | $6,800 | n/a |
$3,034
32,825
kWh
|
$189
-
kW-mo/yr
|
$(-280.0) | - |
04 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $16,090 | $24,980 | n/a |
$17,836
187,573
kWh
|
- | $(-1,746.0) | - |
05 | 2.8114: Change rate schedules or other changes in utility service | $9,857 | $1,060 | n/a | - | - | $9,857 | - |
06 | 4.445: Install equipment to move product | $3,650 | $560 | n/a | - | - | - | $3,650 |
TOTAL RECOMMENDED | $34,379 | $33,870 |
$22,818
240,914
kWh
|
$189
-
kW-mo/yr
|
$7,722 | $3,650 | ||
TOTAL IMPLEMENTED | - | - | - | - | - | - | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Personnel Changes Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs