Assessment Year | 1999 |
---|---|
Principal Product | Sheet Metal Fabrication |
NAICS |
n/a
|
SIC | 3444: Sheet Metal Work |
Sales Range | $1 M to 5M |
# of Employees | 60 |
Plant Area |
22,500
ft2
|
Annual Production | 1,200,000
pieces
|
Production Hrs. Annual | 6,344
hrs
|
Location (State) | Nevada |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $22,908 | 465,416 |
kWh
|
$0.049 |
Electricity Demand | $9,883 | 1,065 |
kW-mo/yr
|
$9.28 |
Electricity Fees | $1,952 | - |
|
- |
Natural Gas | $5,716 | 966 |
MMBtu
|
$5.92 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $9,129 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $3,970 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Natural Gas Savings |
---|---|---|---|---|---|---|---|---|
01 | 2.4221: Install compressor air intakes in coolest locations | $255 | $450 |
$157
3,810
kWh
|
$93
-
kW-mo/yr
|
$5 | - | |
02 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $3,007 | $400 |
$1,842
44,256
kWh
|
$1,106
-
kW-mo/yr
|
$59 | - | |
03 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $932 | $2,270 |
$643
15,533
kWh
|
$271
-
kW-mo/yr
|
$18 | - | |
04 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $4,227 | $6,280 |
$2,917
70,047
kWh
|
$1,227
-
kW-mo/yr
|
$83 | - | |
05 | 2.7243: Improve air circulation with destratification fans / other methods | $708 | $1,391 |
$(-115.0)
(-2,638)
kWh
|
$(-102.0)
-
kW-mo/yr
|
$(-1.0) |
$926
-
MMBtu
|
|
TOTAL RECOMMENDED | $9,129 | $10,791 |
$5,444
131,008
kWh
|
$2,595
-
kW-mo/yr
|
$164 |
$926
-
MMBtu
|
||
TOTAL IMPLEMENTED | $3,970 | $2,241 |
$1,884
45,428
kWh
|
$1,097
-
kW-mo/yr
|
$63 |
$926
-
MMBtu
|
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs