Assessment Year | 1999 |
---|---|
Principal Product | Computer Storage Devices |
NAICS |
n/a
|
SIC | 3572: Computer Storage Devices |
Sales Range | $50 M to 100M |
# of Employees | 130 |
Plant Area |
120,000
ft2
|
Annual Production | 50,250,000
pieces
|
Production Hrs. Annual | 6,240
hrs
|
Location (State) | California |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $127,982 | 2,748,535 |
kWh
|
$0.047 |
Electricity Demand | $53,116 | 6,518 |
kW-mo/yr
|
$8.15 |
Electricity Fees | $16,131 | - |
|
- |
Natural Gas | $28,699 | 4,552 |
MMBtu
|
$6.30 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $18,561 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $4,016 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Solid Waste (non-haz) Savings | Administrative Changes Savings |
---|---|---|---|---|---|---|---|---|---|
01 | 2.4226: Use / purchase optimum sized compressor | $3,174 | $1,500 |
$1,465
31,653
kWh
|
$1,482
-
kW-mo/yr
|
$227 | - | - | |
02 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $3,742 | $900 |
$1,989
42,790
kWh
|
$1,485
-
kW-mo/yr
|
$268 | - | - | |
03 | 2.7241: Install outside air damper / economizer on hvac unit | $10,471 | $15,285 |
$7,846
168,523
kWh
|
$1,860
-
kW-mo/yr
|
$765 | - | - | |
04 | 2.8114: Change rate schedules or other changes in utility service | $274 | - | - | - | - | - | $274 | |
05 | 3.5212: Regrind, reuse, or sell scrap plastic parts | $900 | - | - | - | - |
$900
-
lb
|
- | |
TOTAL RECOMMENDED | $18,561 | $17,685 |
$11,300
242,966
kWh
|
$4,827
-
kW-mo/yr
|
$1,260 |
$900
-
lb
|
$274 | ||
TOTAL IMPLEMENTED | $4,016 | $900 |
$1,989
42,790
kWh
|
$1,485
-
kW-mo/yr
|
$268 | - | $274 |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs