Assessment Year | 1998 |
---|---|
Principal Product | Plastic Products |
NAICS |
n/a
|
SIC | 3089: Plastics Products, Not Elsewhere Classified |
Sales Range | $10 M to 50M |
# of Employees | 170 |
Plant Area |
80,000
ft2
|
Annual Production | 112,000,000
pieces
|
Production Hrs. Annual | 6,240
hrs
|
Location (State) | Nevada |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $144,601 | 3,408,851 |
kWh
|
$0.042 |
Electricity Demand | $60,967 | 7,776 |
kW-mo/yr
|
$7.84 |
Electricity Fees | $8,426 | - |
|
- |
Natural Gas | $21,084 | 3,683 |
MMBtu
|
$5.72 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $173,115 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $140,593 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Natural Gas Savings | Solid Waste (non-haz) Savings | Personnel Changes Savings | Ancillary Material Cost Savings | Water Consumption Savings |
---|---|---|---|---|---|---|---|---|---|---|---|---|
01 | 2.2437: Recover waste heat from equipment | $2,700 | $1,890 | - | - | - |
$2,700
-
MMBtu
|
- | - | - | - | |
02 | 2.2614: Use cooling tower or economizer to replace chiller cooling | $9,271 | $21,600 |
$7,687
181,125
kWh
|
$2,131
-
kW-mo/yr
|
$196 | - | - | - | - |
$(-743.0)
-
Tgal
|
|
03 | 2.2625: Chill water to the highest temperature possible | $2,061 | - |
$1,491
35,170
kWh
|
$530
-
kW-mo/yr
|
$40 | - | - | - | - | - | |
04 | 2.5125: Size air handling grills/ duct/s coils to minimize air resistance | $1,030 | $1,267 |
$745
17,585
kWh
|
$265
-
kW-mo/yr
|
$20 | - | - | - | - | - | |
05 | 2.6221: Use most efficient equipment at it's maximum capacity and less efficient equipment only when necessary | $9,488 | $1,080 |
$4,770
112,544
kWh
|
$4,532
-
kW-mo/yr
|
$186 | - | - | - | - | - | |
06 | 2.6231: Utilize controls to operate equipment only when needed | $322 | $150 |
$316
7,327
kWh
|
- | $6 | - | - | - | - | - | |
07 | 2.7134: Use photocell controls | $1,872 | $490 |
$1,429
33,705
kWh
|
$406
-
kW-mo/yr
|
$37 | - | - | - | - | - | |
08 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $14,676 | $50,495 |
$10,615
250,293
kWh
|
$3,773
-
kW-mo/yr
|
$288 | - | - | - | - | - | |
09 | 2.7231: Use radiant heater for spot heating | $2,679 | $8,064 | - | - | - |
$2,679
-
MMBtu
|
- | - | - | - | |
10 | 4.621: Use fixtures to reduce machine changeout times | $52,000 | $14,200 | - | - | - | - | - | - | $52,000 | - | |
11 | 3.1192: Reduce scrap production | $12,952 | $75,000 |
$4,368
102,872
kWh
|
$1,552
-
kW-mo/yr
|
- | - |
$792
-
lb
|
$6,240 | - | - | |
12 | 3.1192: Reduce scrap production | $64,064 | $375,750 | - | - | - | - |
$64,064
-
lb
|
- | - | - | |
TOTAL RECOMMENDED | $173,115 | $549,986 |
$31,421
740,621
kWh
|
$13,189
-
kW-mo/yr
|
$773 |
$5,379
-
MMBtu
|
$64,856
-
lb
|
$6,240 | $52,000 |
$(-743.0)
-
Tgal
|
||
TOTAL IMPLEMENTED | $140,593 | $421,961 |
$14,693
346,424
kWh
|
$7,458
-
kW-mo/yr
|
$442 |
$2,679
-
MMBtu
|
$64,064
-
lb
|
- | $52,000 |
$(-743.0)
-
Tgal
|
||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Natural Gas Savings | Solid Waste (non-haz) Savings | Personnel Changes Savings | Ancillary Material Cost Savings | Water Consumption Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs