Assessment Year | 1998 |
---|---|
Principal Product | Dimension Lumber |
NAICS |
n/a
|
SIC | 2421: Sawmills and Planing Mills, General |
Sales Range | $10 M to 50M |
# of Employees | 105 |
Plant Area |
252,100
ft2
|
Annual Production | 41,000,000
units
|
Production Hrs. Annual | 2,470
hrs
|
Location (State) | California |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $366,956 | 6,291,911 |
kWh
|
$0.058 |
Electricity Demand | $196,577 | 57,768 |
kW-mo/yr
|
$3.40 |
Electricity Fees | $(-22,228.0) | - |
|
- |
Natural Gas | $169,015 | 140,588 |
MMBtu
|
$1.20 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $152,497 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $2,942 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Natural Gas Savings | Administrative Changes Savings | Primary Product Savings | By-product Production Savings |
---|---|---|---|---|---|---|---|---|---|---|---|
01 | 2.2121: Increase amount of condensate returned | $6,487 | $6,000 | - | - | - |
$6,487
-
MMBtu
|
- | - | - | |
02 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $248 | $200 |
$272
4,689
kWh
|
- | $(-24.0) | - | - | - | - | |
03 | 2.3212: Optimize plant power factor | $5,011 | $16,200 | - | - | $5,011 | - | - | - | - | |
04 | 2.4133: Use most efficient type of electric motors | $1,858 | $3,052 |
$1,248
21,688
kWh
|
$720
-
kW-mo/yr
|
$(-110.0) | - | - | - | - | |
05 | 2.2511: Insulate bare equipment | $1,575 | $530 | - | - | - |
$1,575
-
MMBtu
|
- | - | - | |
06 | 2.2511: Insulate bare equipment | $878 | $611 | - | - | - |
$878
-
MMBtu
|
- | - | - | |
07 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $836 | $306 |
$691
12,016
kWh
|
$206
-
kW-mo/yr
|
$(-61.0) | - | - | - | - | |
08 | 2.7134: Use photocell controls | $713 | $290 |
$663
23,154
kWh
|
$108
-
kW-mo/yr
|
$(-58.0) | - | - | - | - | |
09 | 2.7134: Use photocell controls | $2,820 | $580 |
$2,560
44,549
kWh
|
$485
-
kW-mo/yr
|
$(-225.0) | - | - | - | - | |
10 | 2.7261: Install timers and/or thermostats | $252 | $150 |
$253
3,224
kWh
|
- | $(-1.0) | - | - | - | - | |
11 | 3.5313: Increase amount of waste recovered for resale | $326 | - | - | - | - | - | $326 | - | - | |
12 | 2.2437: Recover waste heat from equipment | $129,993 | $113,670 | - | - | - |
$27,193
-
MMBtu
|
- | $78,000 | $24,800 | |
13 | 3.5242: Recover metals from spent solutions and recycle | $1,500 | - | - | - | - | - | $1,500 | - | - | |
TOTAL RECOMMENDED | $152,497 | $141,589 |
$5,687
109,320
kWh
|
$1,519
-
kW-mo/yr
|
$4,532 |
$36,133
-
MMBtu
|
$1,826 | $78,000 | $24,800 | ||
TOTAL IMPLEMENTED | $2,942 | $3,558 |
$2,211
38,393
kWh
|
$926
-
kW-mo/yr
|
$(-195.0) | - | - | - | - | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Natural Gas Savings | Administrative Changes Savings | Primary Product Savings | By-product Production Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs