Assessment Year | 1997 |
---|---|
Principal Product | Measuring & Controlling Devices |
NAICS |
n/a
|
SIC | 3829: Measuring and Controlling Devices, Not Elsewhere Classified |
Sales Range | $100 M to 500M |
# of Employees | 600 |
Plant Area |
92,410
ft2
|
Annual Production | 1,560,000
pieces
|
Production Hrs. Annual | 4,508
hrs
|
Location (State) | Nevada |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $100,347 | 2,169,988 |
kWh
|
$0.046 |
Electricity Demand | $51,605 | 12,661 |
kW-mo/yr
|
$4.08 |
Electricity Fees | $(-350.0) | - |
|
- |
Natural Gas | $8,720 | 1,650 |
MMBtu
|
$5.28 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $6,242 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | - |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings |
---|---|---|---|---|---|---|
01 | 2.7134: Use photocell controls | $199 | $180 |
$137
2,931
kWh
|
$62
-
kW-mo/yr
|
|
02 | 2.7111: Reduce illumination to minimum necessary levels | $510 | $138 |
$349
7,620
kWh
|
$161
-
kW-mo/yr
|
|
03 | 2.7135: Install occupancy sensors | $2,072 | $1,148 |
$1,791
38,687
kWh
|
$281
-
kW-mo/yr
|
|
04 | 2.7111: Reduce illumination to minimum necessary levels | $1,500 | $472 |
$1,154
24,912
kWh
|
$346
-
kW-mo/yr
|
|
05 | 2.4221: Install compressor air intakes in coolest locations | $398 | $290 |
$398
8,499
kWh
|
- | |
06 | 2.6231: Utilize controls to operate equipment only when needed | $1,563 | $1,350 |
$1,266
27,550
kWh
|
$297
-
kW-mo/yr
|
|
TOTAL RECOMMENDED | $6,242 | $3,578 |
$5,095
110,199
kWh
|
$1,147
-
kW-mo/yr
|
||
TOTAL IMPLEMENTED | - | - | - | - | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs