Assessment Year | 1996 |
---|---|
Principal Product | Beer and Ale |
NAICS |
n/a
|
SIC | 2082: Malt Beverages |
Sales Range | $10 M to 50M |
# of Employees | 68 |
Plant Area |
78,000
ft2
|
Annual Production | 250,000
bbl
|
Production Hrs. Annual | 8,760
hrs
|
Location (State) | California |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $225,175 | 2,981,536 |
kWh
|
$0.076 |
Electricity Demand | $32,238 | 7,599 |
kW-mo/yr
|
$4.24 |
Electricity Fees | $17,198 | - |
|
- |
Natural Gas | $167,491 | 32,128 |
MMBtu
|
$5.21 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $79,118 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $25,435 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Natural Gas Savings | Water Disposal Savings | Primary Raw Material Savings |
---|---|---|---|---|---|---|---|---|---|---|
01 | 2.4133: Use most efficient type of electric motors | $11,359 | $766 |
$10,362
121,043
kWh
|
$560
-
kW-mo/yr
|
$437 | - | - | - | |
02 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $1,715 | $200 |
$1,649
19,343
kWh
|
- | $66 | - | - | - | |
03 | 2.7134: Use photocell controls | $795 | $156 |
$723
8,499
kWh
|
$41
-
kW-mo/yr
|
$31 | - | - | - | |
04 | 2.7135: Install occupancy sensors | $4,438 | $558 |
$4,012
46,893
kWh
|
$255
-
kW-mo/yr
|
$171 | - | - | - | |
05 | 2.4221: Install compressor air intakes in coolest locations | $349 | $240 |
$336
3,810
kWh
|
- | $13 | - | - | - | |
06 | 2.4231: Reduce the pressure of compressed air to the minimum required | $1,021 | - |
$982
11,430
kWh
|
- | $39 | - | - | - | |
07 | 2.8114: Change rate schedules or other changes in utility service | $5,739 | - | - |
$(-67,204.0)
-
kW-mo/yr
|
$72,943 | - | - | - | |
08 | 2.2511: Insulate bare equipment | $6,756 | $890 | - | - | - |
$6,756
-
MMBtu
|
- | - | |
09 | 4.212: Adopt in-house material generation | $46,800 | $600 | - | - | - | - | - | $46,800 | |
10 | 3.4154: Eliminate leaks in water lines and valves | $146 | $23 | - | - | - | - |
$146
-
Tgal
|
- | |
TOTAL RECOMMENDED | $79,118 | $3,433 |
$18,064
211,018
kWh
|
$(-66,348.0)
-
kW-mo/yr
|
$73,700 |
$6,756
-
MMBtu
|
$146
-
Tgal
|
$46,800 | ||
TOTAL IMPLEMENTED | $25,435 | $2,437 |
$17,005
198,709
kWh
|
$815
-
kW-mo/yr
|
$713 |
$6,756
-
MMBtu
|
$146
-
Tgal
|
- | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Natural Gas Savings | Water Disposal Savings | Primary Raw Material Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs