| Assessment Year | 1995 |
|---|---|
| Principal Product | Wood Strips and Mouldings |
| NAICS |
n/a
|
| SIC | 2431: Millwork |
| Sales Range | $5 M to 10M |
| # of Employees | 70 |
| Plant Area |
70,000
ft2
|
| Annual Production | 9,600,000
units
|
| Production Hrs. Annual | 1,700
hrs
|
| Location (State) | California |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $254,108 | 2,100,528 |
kWh
|
$0.12 |
| TOTAL YEARLY COSTS | - | |||
| RECOMMENDED SAVINGS* | $15,867 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | $13,213 | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings |
|---|---|---|---|---|---|
| 01 | 2.4133: Use most efficient type of electric motors | $2,750 | $688 |
$2,750
23,154
kWh
|
|
| 02 | 2.3212: Optimize plant power factor | $2,654 | $5,355 |
$2,654
-
kWh
|
|
| 03 | 2.7121: Utilize daylight whenever possible in lieu of artificial light | $4,969 | $275 |
$4,969
41,911
kWh
|
|
| 04 | 2.7121: Utilize daylight whenever possible in lieu of artificial light | $1,474 | $280 |
$1,474
12,603
kWh
|
|
| 05 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $652 | $240 |
$652
9,965
kWh
|
|
| 06 | 2.7261: Install timers and/or thermostats | $1,088 | $192 |
$1,088
13,189
kWh
|
|
| 07 | 2.6212: Turn off equipment during breaks, reduce operating time | $2,280 | - |
$2,280
34,877
kWh
|
|
| TOTAL RECOMMENDED | $15,867 | $7,030 |
$15,867
135,699
kWh
|
||
| TOTAL IMPLEMENTED | $13,213 | $1,675 |
$13,213
135,699
kWh
|
||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs