Assessment Year | 1994 |
---|---|
Principal Product | Plastic Cups |
NAICS |
n/a
|
SIC | 2759: Commercial Printing, Not Elsewhere Classified |
Sales Range | $1 M to 5M |
# of Employees | 160 |
Plant Area |
300,000
ft2
|
Annual Production | 1,300,000
pieces
|
Production Hrs. Annual | 6,240
hrs
|
Location (State) | Nevada |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $534,615 | 8,529,015 |
kWh
|
$0.063 |
Natural Gas | $10,085 | 2,336 |
MMBtu
|
$4.32 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $68,624 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $54,969 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Natural Gas Savings |
---|---|---|---|---|---|---|
01 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $21,106 | $1,200 |
$21,106
336,753
kWh
|
- | |
02 | 2.4221: Install compressor air intakes in coolest locations | $1,838 | $100 |
$1,838
29,308
kWh
|
- | |
03 | 2.2524: Avoid cooling of process streams or materials that must subsequently be heated | $13,655 | $5,000 |
$13,655
217,761
kWh
|
- | |
04 | 2.4133: Use most efficient type of electric motors | $20,542 | $25,047 |
$20,542
328,546
kWh
|
- | |
05 | 2.7243: Improve air circulation with destratification fans / other methods | $1,646 | $2,200 | - |
$1,646
-
MMBtu
|
|
06 | 2.7135: Install occupancy sensors | $2,237 | $80 |
$2,237
35,756
kWh
|
- | |
07 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $7,600 | - |
$7,600
120,750
kWh
|
- | |
TOTAL RECOMMENDED | $68,624 | $33,627 |
$66,978
1,068,874
kWh
|
$1,646
-
MMBtu
|
||
TOTAL IMPLEMENTED | $54,969 | $28,627 |
$53,323
851,113
kWh
|
$1,646
-
MMBtu
|
||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Natural Gas Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs