Assessment Year | 2023 |
---|---|
Principal Product | Paper Food Cartons |
NAICS | 322212: Folding Paperboard Box Manufacturing |
SIC | 2656: Sanitary Food Containers, Except Folding |
Sales Range | $10 M to 50M |
# of Employees | 150 |
Plant Area |
133,732
ft2
|
Annual Production | 260,000,000
units
|
Production Hrs. Annual | 8,760
hrs
|
Location (State) | Nebraska |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | ||
---|---|---|---|---|---|
Electricity Usage | $269,243 | 5,205,200 |
kWh
|
$0.052 | |
Electricity Demand | $89,131 | 11,481 |
kW-mo/yr
|
$7.76 | |
Natural Gas | $27,399 | 4,256 |
MMBtu
|
$6.44 | |
Waste Disposal Costs | |||||
Water Usage | $1,407 | 396 |
Tgal
|
$3.55 | |
Water Disposal | $1,705 | 396 |
Tgal
|
$4.30 | |
TOTAL YEARLY COSTS | $388,885 | ||||
RECOMMENDED SAVINGS* | $71,284 |
See individual recommendations below
*Non-energy impacts included in savings.
|
|||
IMPLEMENTED SAVINGS* | $71,284 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Personnel Changes Savings | Ancillary Material Cost Savings | Increase in Production Savings |
---|---|---|---|---|---|---|---|---|---|
01 | 2.7243: Improve air circulation with destratification fans / other methods | $30,717 | $54,394 |
$4,578
88,038
kWh
|
$939
-
kW-mo/yr
|
- | - | $25,200 | |
02 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $11,509 | $4,500 |
$12,121
233,094
kWh
|
- | $(-512.0) | $(-100.0) | - | |
03 | 2.4239: Eliminate or reduce compressed air usage | $9,699 | $10,600 |
$7,870
151,344
kWh
|
$1,829
-
kW-mo/yr
|
- | - | - | |
04 | 2.4239: Eliminate or reduce compressed air usage | $6,949 | $768 | - |
$6,949
-
kW-mo/yr
|
- | - | - | |
05 | 2.4239: Eliminate or reduce compressed air usage | $4,292 | $128 |
$4,292
82,547
kWh
|
- | - | - | - | |
06 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $3,953 | $392 |
$3,953
76,452
kWh
|
- | - | - | - | |
07 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $2,356 | $2,892 |
$1,774
34,121
kWh
|
$377
-
kW-mo/yr
|
$205 | - | - | |
08 | 2.4221: Install compressor air intakes in coolest locations | $1,809 | $2,875 |
$1,809
34,793
kWh
|
- | - | - | - | |
TOTAL RECOMMENDED | $71,284 | $76,549 |
$36,397
700,389
kWh
|
$10,094
-
kW-mo/yr
|
$(-307.0) | $(-100.0) | $25,200 | ||
TOTAL IMPLEMENTED | $71,284 | $76,549 |
$36,397
700,389
kWh
|
$10,094
-
kW-mo/yr
|
$(-307.0) | $(-100.0) | $25,200 | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Personnel Changes Savings | Ancillary Material Cost Savings | Increase in Production Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs