ITAC Assessment: NL0069
ITAC logo
ITAC Assessment: NL0069
Grant Funding Opportunity NOW OPEN
Up to $300k at 50% cost share for qualifying* projects.
Grant Funding Opportunity Open
Qualifying* small and medium-sized US manufacturers, that received an ITAC, Onsite Energy/CHP TAP, or qualified equivalent assessment since 2018 can now apply for grants for implementation of assessment recommendations at up to 50% of qualifying* project costs with a maximum of $300,000 per grant.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
Assessment Year 2022
Principal Product Medical Devices
NAICS 339112: Surgical and Medical Instrument Manufacturing
SIC 3841: Surgical and Medical Instruments and Apparatus
Sales Range $50
M
to 100
M
# of Employees 650
Plant Area 350,000
ft2
Annual Production 10,000,000
units
Production Hrs. Annual 8,280
hrs
Location (State) Nebraska

Facility Energy Cost and Usage

Source Yearly Cost Usage
Electricity Usage $1,398,940 51,744,000
kWh
Electricity Demand $1,456,741 84,394
kW-mo/yr
Electricity Fees $285,328 -
Waste Disposal Costs
Water Usage $44,680 3,439
Tgal
Water Disposal $45,894 1,708
Tgal
Solid Waste (non-haz) $49,500 275,000
lb
TOTAL YEARLY COSTS $3,281,082
RECOMMENDED SAVINGS* $647,594 *Non-energy impacts included in savings.
IMPLEMENTED SAVINGS* -

Recommendations

# Description Yearly Savings* Imp'd Cost* Status Electricity Usage Savings Electricity Demand Savings Solid Waste (non-haz) Savings Personnel Changes Savings One-time Revenue or Avoided Cost Savings
01 2.2622: Replace existing chiller with high efficiency model $459,130 $2,266,822 $3,130
115,920
kWh
- - - $456,000
02 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves $100,270 $900 $100,270
3,770,723
kWh
- - - -
03 2.4224: Upgrade controls on compressors $64,154 $20,000 $34,122
1,263,789
kWh
$30,032
-
kW-mo/yr
- - -
04 2.7232: Replace existing hvac unit with high efficiency model $11,908 $110,400 $11,908
441,051
kWh
- - - -
05 3.5311: Recover and reuse waste material $10,312 $3,180 - - $9,900
-
lb
$412 -
06 2.4111: Utilize energy-efficient belts and other improved mechanisms $1,221 $1,069 $650
24,060
kWh
$571
-
kW-mo/yr
- - -
07 2.7142: Utilize higher efficiency lamps and/or ballasts $599 $1,397 $208
7,557
kWh
$391
-
kW-mo/yr
- - -
TOTAL RECOMMENDED $647,594 $2,403,768 $150,288
5,623,100
kWh
$30,994
-
kW-mo/yr
$9,900
-
lb
$412 $456,000
TOTAL IMPLEMENTED - - - - - - -
Yearly Savings* Imp'd Cost* Electricity Usage Savings Electricity Demand Savings Solid Waste (non-haz) Savings Personnel Changes Savings One-time Revenue or Avoided Cost Savings
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs