Assessment Year | 2021 |
---|---|
Principal Product | Mailbox Units |
NAICS | 332999: All Other Miscellaneous Fabricated Metal Product Manufacturing |
SIC | 3499: Fabricated Metal Products, Not Elsewhere Classified |
Sales Range | $100 M to 500M |
# of Employees | 260 |
Plant Area |
200,000
ft2
|
Annual Production | 118,000
units
|
Production Hrs. Annual | 2,200
hrs
|
Location (State) | Kansas |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | ||
---|---|---|---|---|---|
Electricity Usage | $130,664 | 3,898,640 |
kWh
|
$0.034 | |
Electricity Demand | $269,509 | 12,937 |
kW-mo/yr
|
$20.83 | |
Electricity Fees | $40,318 | - |
|
- | |
Natural Gas | $91,474 | 26,129 |
MMBtu
|
$3.50 | |
Waste Disposal Costs | |||||
Water Usage | $18,447 | 5,290 |
Tgal
|
$3.49 | |
Water Disposal | $29,802 | 5,290 |
Tgal
|
$5.63 | |
TOTAL YEARLY COSTS | $580,213 | ||||
RECOMMENDED SAVINGS* | $55,051 |
See individual recommendations below
*Non-energy impacts included in savings.
|
|||
IMPLEMENTED SAVINGS* | - |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Natural Gas Savings | Personnel Changes Savings | Ancillary Material Cost Savings | One-time Revenue or Avoided Cost Savings |
---|---|---|---|---|---|---|---|---|---|---|---|
01 | 2.3212: Optimize plant power factor | $16,506 | $12,500 | - | - | $16,506 | - | - | - | - | |
02 | 2.7444: Close holes and openings in building such as broken windows | $8,000 | $16,000 | - | - | - | - | - | - | $8,000 | |
03 | 2.7241: Install outside air damper / economizer on hvac unit | $7,166 | $12,910 |
$7,166
210,762
kWh
|
- | - | - | - | - | - | |
04 | 2.2437: Recover waste heat from equipment | $6,837 | $18,456 | - | - | - |
$6,837
-
MMBtu
|
- | - | - | |
05 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $5,098 | $4,000 |
$6,084
178,943
kWh
|
- | - | - | $(-736.0) | $(-250.0) | - | |
06 | 2.2522: Isolate hot or cold equipment | $3,823 | $1,018 |
$(-127.0)
(-3,740)
kWh
|
- | - |
$3,950
-
MMBtu
|
- | - | - | |
07 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $3,528 | $7,371 |
$955
28,097
kWh
|
$2,573
-
kW-mo/yr
|
- | - | - | - | - | |
08 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $2,217 | $1,920 |
$2,072
60,948
kWh
|
$145
-
kW-mo/yr
|
- | - | - | - | - | |
09 | 3.5311: Recover and reuse waste material | $1,876 | $6,000 | - | - | - | - | $382 | $1,494 | - | |
TOTAL RECOMMENDED | $55,051 | $80,175 |
$16,150
475,010
kWh
|
$2,718
-
kW-mo/yr
|
$16,506 |
$10,787
-
MMBtu
|
$(-354.0) | $1,244 | $8,000 | ||
TOTAL IMPLEMENTED | - | - | - | - | - | - | - | - | - | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Natural Gas Savings | Personnel Changes Savings | Ancillary Material Cost Savings | One-time Revenue or Avoided Cost Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs